HP 10000 G2 Series Installation Manual page 61

Rack options
Hide thumbs Also See for HP 10000 G2 Series:
Table of Contents

Advertisement

Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the extension
3.
kit and tighten.
From the side panel grounding lug to the bottom panel grounding lug:
Place the 36.83-cm (14.5 in) grounding strap over the grounding lug on the side panel of the extension
1.
kit.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the side panel
2.
of the extension kit and tighten.
Repeat the previous steps to secure the other end of the same grounding strap to the grounding lug on
3.
the bottom panel of the extension kit.
From the egress panel grounding lug to the bottom panel grounding lug:
Place the 36.83-cm (14.5 in) grounding strap over the grounding lug on the egress panel of the
1.
extension kit.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the egress
2.
panel of the extension kit and tighten.
Ground Bonding kit 61