10.36 Octal Relay Module Output Programming

10.36.1 Follow Action: Program Addresses (2740-2771)

To program an Octal Relay Module for Follow Action, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 1 for Follow Action.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
The Octal Relay Module is the DS7488. See section 1.18 and 6.4 for further details.
NOTE:
If a DS9484 is used, it replaces the DS7488 and takes up outputs 1-4 of the Octal Relay Module. Outputs 5-8 of the Octal Relay
Module are unavailable. If two DS9484 power supplies are used, one replaces Octal Relay Module 1 and the other replaces
Octal Relay Module 2.
For Octal Relay Partition Assignment, see section 10.36.5.
Program Address A
Data Digit
1
2
1
SELECT OPTION DD 2
Follows
0 1 2
3
Disabled
Burglar Alarm
Fire Alarm
Page 60
P/N: F01U035325-01
Octal
DS7488-1
DS7488-1
Relay
Address
Address
#
A
B
1
2740
2741
2
2742
2743
3
2744
2745
4
2746
2747
5
2748
2749
6
2750
2751
7
2752
2753
8
2754
2755
9
2756
2757
10
2758
2759
11
2760
2761
12
2762
2763
13
2764
2765
14
2766
2767
15
2768
2769
16
2770
2771
** = This includes invisible zones. See glossary for further details.
*** = See section 6.4 for description of this option.
Copyright © 2007 Bosch Security Systems, Inc.
Program Address B
Data Digit
1
2
SELECT OPTION DD 1 & 2
Latch ON after Zone Alarm**
ON during Entry Pre-Alert
ON for 10 sec. after pressing [System Reset]
ON for Any Armed state
Ground Start
System Status (Ready to Arm)
Zone Alarm
Zone Alarm delayed by 20 seconds
Keypad Sounder Output
Access Output (10 sec. pulse)
Future Selection
Panic/Duress Output***
ON when System is Partial
ON when System is Fully Armed
DS7400Xi (4+) Reference Guide
DD
0 0
0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
0*0
0*1
0*2
0*3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds7445Ds7445iDs7447Ds7447e

Table of Contents