11.4
General System Requirements
Applies to the following grades only:
Local Burglary
Grade A using Digital Alarm Communicator
Alarm -
Transmitter (DACT)
Police Station
Grades AA and A using DACT and DS7416i
Connection -
Communications module.
Grade A using DACT and local Bell.
Central Station
Grades AA and A using DACT and DS7416i
Burglary Alarm -
Communications module.
Grade B using DACT and local bell.
Grade C using Digital Alarm Communicator
Transmitter only.
The controls must be installed in accordance with UL Standards
UL681 and UL609 for all grades of service.
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
• Open Report (Program Address 3331) must be programmed.
• Close Report (Program Address 3332) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 3340 and 3347)
must be programmed.
2. General Control Programming:
• The control must not be programmed for auto disarm.
• Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
3. Zone Function Programming:
• The Burglar alarm signal (whether pulsed or steady) must be
different from the Fire alarm signal.
4. Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2 = 3.
• Program Address 2737 must be programmed as: Data Digit 1=
8.

11.4.1Local Burglary Alarm

A. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System's model AE3CC
enclosure with a cover actuated tamper switch installed.
• An Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4029) must
be programmed for not longer than 60 seconds.

11.4.2Police Station Connection

Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems' model AE3CC
enclosure with a cover actuated tamper switch installed.
DS7400Xi ( 4+) Reference Guide
• An DS7416i (or DataTAC) interface module.
• The DS7416i module and antenna should be mounted within
the protected area.
• The Detection Systems' model DS7481 Phone Line Monitor.
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B.Grade A Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System's model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.

11.4.3Central Station Burglary Alarm and Proprietary

A.Central Station Burglary Grades AA and A and Proprietary
Grade AA Installations Using an DS7416i Interface Module
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems' model AE3CC
enclosure with a cover actuated tamper switch installed.
• An DS7416i (or DataTAC) interface module.
• The DS7416i module and antenna should be mounted within
the protected area.
• The Detection Systems' model DS7481 Phone Line Monitor.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B.Grade B Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems' model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
C.Central Station Burglary Grade C and Proprietary Grade A
Installations Using Digital Alarm Communicator Transmitter only
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System's model AE3CC
enclosure with a cover actuated tamper switch installed.
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
Copyright © 2007 Bosch Security Systems, Inc.
P/N: F01U035325-01
Page 77