16. STANDBY BATTERY REQUIREMENTS

The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Simplicity Fire Alarm
System
Device
SIMPLICITY 64 Fire Alarm Panel
SIMPLICITY 126 Fire Alarm Panel
Premier Addressable REPEATER PANEL
Fyreye Addressable Ionisation Smoke Detector
Fyreye Addressable Optical Smoke Detector
Fyreye Addressable Heat Detector
Fyreye Addressable High Temperature Heat Detector
Fyreye Addressable Multi-point Detector
Fyreye Addressable Sounder Base
Zeta Addressable Call Point (EN54)
Zeta Addressable Call Point
Zeta Weatherproof Addressable Call Point
Zeta Input Unit
Zeta Input Output Unit
Zeta Sounder Control Module
Zone Monitor Unit
Fyreye Addressable Beam Detector (5-50m)
Fyreye Addressable Beam Detector (50-100m)
Zeta Addressable Maxitone Sounder
Zeta Addressable Miditone Sounder
Zeta Addressable Securetone Sounder
Zeta Addressable Remote LED Indicator
Conventional Sounders (via a sounder Control Circuit)
Zeta Conventional Maxitone Sounder
Zeta Conventional Miditone Sounder
Zeta Conventional Securetone Sounder
Zeta Conventional Megatone Sounder
Zeta Conventional Flasher
Zeta Conventional Sounder Flasher
Zeta Conventional 6" Bells
Zeta Conventional 8" Bells
Conventional Detectors (via a Zone Monitor)
Fyreye Conventional Optical Detector
Fyreye Conventional Heat Detector (A1R)
Fyreye Conventional Heat Detector (CS)
* The Simplicity can only power 1 repeater. Any subsequent ones will need a separate power supply.
Approved Document No: GLT.MAN-107
Issue : 2.00
Authorised: GH
Date: 4/06/2007
Software:PANEL:R1107 & LOOP:R1062
Product Code
I
q
(mA)
SP-64
100
SP-126
100
REP-AD
200
FEAI2000
0.6
FEAO2000
0.6
FEAH2000
0.6
FEAHH2000
0.6
FEAOH2000
0.6
FEA-SB
0
ZT-CP2/AD
0.5
ZT-MCP/AD
0.4
ZT-
0.4
MCP/AD/WP
ZIU
2
ZIOU
2
ZSCC
2
ZT-ZM
6
ZT-50RA
t.b.c.
ZT-100RA
t.b.c.
ZAMT
1.5
ZAMD
1.5
ZAST
1.5
ZTA/LE2
1.5
ZMT/8
0
ZMD/8
0
ZST/8
0
ZIDC
0
ZFL2RR
0
ZLT/8RR
0
ZTB6B/24
0
ZTB8B
0
FEO2000
0.06
FEHR2000
0.04
FEFH2000
0.04
I
I
Max
flt
alm
(mA)
(mA)
per
Loop
150
200
N/A
150
200
N/A
220
220
N/A
N/A
2
126
N/A
2
126
N/A
2
126
N/A
2
126
N/A
2
126
N/a
10
32
N/a
3
126
N/a
13
126
N/a
13
126
2
2.5
126
2
10
16
2
10
16
8-30
22
10
t.b.c.
t.b.c.
t.b.c.
t.b.c.
t.b.c.
t.b.c.
N/a
9
32
N/a
9
32
N/a
9
32
N/a
10
32
N/a
15
N/a
N/a
15
N/a
N/a
15
N/a
N/a
200
N/a
N/a
90
N/a
N/a
110
N/a
N/a
25
N/a
N/a
35
N/a
N/a
25
N/a
N/a
25
N/a
N/a
25
N/a
PAGE 28
Max
per
System
1
1
4*
126
126
126
126
126
32
126
126
126
126
16
16
10
t.b.c.
t.b.c.
64
64
64
64
N/a
N/a
N/a
N/a
N/a
N/a
N/a
N/a
N/a
N/a
N/a