Configuring The Simplicity Fire Alarm Panel; Configuring The Loops - Zeta SP-64,126 Installation Manual

64 or 126 device capacity, single loop analogue addresable fire alarm control panel
Table of Contents

Advertisement

SIMPLICITY INSTALLATION MANUAL.

12. CONFIGURING THE SIMPLICITY FIRE ALARM PANEL

12.1 CONFIGURING THE LOOPS

1 After the system has been installed, and the cabling
checked and the addresses of each device set, connect
the loop to the fire alarm panel and power up the system
(mains & batteries). It should say "system normal, and only
the green Power LED will be lit.
2. Turn the keyswitch to the Controls Enabled Position.
The controls Active LED will light.
3. Press Enter button. This will bring up Configuration
Menu 1 (the user menu). In this Menu there are options to
view loop contents, view the status of each device, or
view the event log. The arrow in the bottom left hand
corner shows that pressing NEXT will bring up a new
screen
4. Press NEXT button. This will prompt for the access
code to enter Configuration Menu 2 (the engineer menu).
The access code for the Simplicity is 369
5. The panel now shows Configuration Menu 2. In this
menu there are options to Configure the loops, to edit
each device, and to configure the system options. The
arrow in the bottom left hand corner shows that pressing
PREVIOUS button will return to Configuration Menu 1
6. Press button 4 to configure the loop. The panel
displays configuration in progress, Please wait. It will
return to Configuration Menu 2 when completed.
7. Press PREVIOUS button, followed by button 1 to view
the loop contents. It lists the number of each type of
device, the number of Double Addresses (DAD) on the
system, the loop number (Loop 1 only), and the total
number of devices on that loop.Check that the number
of devices seen compares to the number expected. If it
is different, refer to the fault finding guide.
8. The panel is now configured, and will function as a basic system, (press Cancel until screen shows system
normal to run the panel), but it is more useful to enter device labels, to give a more precise location of an alarm
device. We recommend that the device labels be entered to allow the panel to be more user friendly during
normal operation.
9. To add a label, go to configuration menu 2 as
described above. Select option 5 to Edit Device. Use
Next / Previous to select the first device to edit. Press
Enter, and a cursor will appear at the start of the 3
Type in the 20 character label for this device, using the
caps lock as necessary.
10. Press enter when the label has been entered.
11. To skip many addresses, press 1 (for loop 1).
The Panel will then prompt for the address. Type the
address and press enter. The panel will now jump to this
address.
The sounder symbol in the top right hand corner shows that this
detector might have an "associated sounder base" connected. The
panel will send the "activate base sounder" command to this address in the event of an alarm. See Sounder
section & Sounder base setup for further information.
Approved Document No: GLT.MAN-107
Issue : 2.00
Authorised: GH
rd
line.
Date: 4/06/2007
Software:PANEL:R1107 & LOOP:R1062
Fire Alarm Panel
To EN54
pt2 & pt4
System Normal
15-01-2006 12:59
Configuration Menu 1
1:Loop Contents
2:Device Status
3:Event logs
Enter Access Code
***
Configuration Menu 2
4:Configure Loops
5:Edit Device
6:Config System
Configuration in
Progress
Please Wait
CO
00
SCC 14
DAD 00
I/O 03
ION 02
ZMU 01
OPT 45
Loop 1
HET 07
BGU 05
Tot 77
Optical
Analog:
25
Normal
Zone:01
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Enter Loop Address
Loop:
1
Address: 100
>
<
Ad:016
Ad:016
PAGE 18