SIMPLICITY INSTALLATION MANUAL.

17. PCB TERMINATION CONNECTIONS.

10
11

17.1 CONNECTIONS

Connection No
Description
1
LOOP 1A +&-
2
LOOP 1B +&-
3
FIRE REPEAT OUTPUT
4
FAULT REPEAT OUTPUT
5
CLASS CHANGE
6
AUX SUP +&-
7
BATTERY + & -
8
THERMISTOR
9
AC AC
10
CONN 27
11
CONN 3
12
CONN 29
13
CONN 6

17.2 FUSES

FUSE NO
DESCRIPTION
FS1
Charger Fuse
FS2
Battery Fuse
FS3
Aux Supply
INLET FUSE
Mains Protection Fuse
Approved Document No: GLT.MAN-107
Issue : 2.00
Authorised: GH
CLASS
LOOP WIRING
FLT REP
CHANGE
+
+
+
+
A-
A+
B-
B+
1 2 3 4 5 6
FS3
Date: 4/06/2007
FS1 FS2
7 8 9
+
Use
Connect to loop 1 side A
Connect to loop 1 side B
24V on fire (including test mode). Use to drive relay.
Normally powered. 0V on fault. Use to drive FLT relay.
Join terminals to activate sounders
24 volt supply. 100mA Max
Connect 2 x 12V SLA batteries in SERIES (ie 24V)
Thermistor to prevent thermal overcharge
Connected to transformer secondary (30VAC)
EARTH connection to display PCB & SCREEN TAG
50 way ribbon cable to display PCB
Filtered mains to transformer
MAINS TERMINAL BLOCK
RATING
1.6A time delay 5 x 20mm glass
1.6A time delay 5 x 20mm glass
100mA time delay 5 x 20mm glass
2.0A Quick Blow HBC 5 x 20mm ceramic
Software:PANEL:R1107 & LOOP:R1062
13
12
CONN29
LIVE NEUT- EARTH
RAL
PAGE 30