Specific Device Wiring Instructions - Zeta SP-64,126 Installation Manual

64 or 126 device capacity, single loop analogue addresable fire alarm control panel
Table of Contents

Advertisement

SIMPLICITY INSTALLATION MANUAL.

7.1 SPECIFIC DEVICE WIRING INSTRUCTIONS

Fyreye Common Base
FE-CB
80-050
LOOP - IN
LOOP + IN
Fyreye Loop Isolator Base
FE-IB
80-090
-
LOOP - IN
LOOP + IN
Fyreye Addressable Sounder Base
FEA-SB
80-100
LOOP - IN
LOOP + IN
Approved Document No: GLT.MAN-107
Issue : 2.00
Authorised: GH
LOOP - OUT
LOOP + OUT
- -
+ +
IN
OUT
LOOP - OUT
LOOP + OUT
LOOP - OUT
LOOP + OUT
Date: 4/06/2007
Software:PANEL:R1107 & LOOP:R1062
Fyreye Addressable Detector Relay Base
FEA-RB
80-080
LOOP - IN
LOOP + IN
Note that on the Fyreye Loop Isolator Base, the
loop wiring connects to the terminal block on the
PCB and NOT to the Base Spring Screws.
The terminals are marked + & - in,
and +,- &- out.
The second –ve contact can be used
during commissioning to check the loop
integrity.
(Connect the –in to the spare – out.
Repeat for all isolators. Measure –ve line
resistance with a DVM. Return the –in
cable to its original terminal block when
tests completed.)
Zeta Manual Call Point (Resetable)
ZT-CP2/AD
43-305
LOOP - IN
LOOP + IN
LOOP - OUT
C
RELAY
OUTPUT
LOOP + OUT
LOOP - OUT
LOOP + OUT
PAGE 10