Installation Procedure For Nec Rack/Third Vendor's Rack - NEC Express5800/120Rh-2 User Manual

Nec servers user's guide
Hide thumbs Also See for Express5800/120Rh-2:
Table of Contents

Advertisement

Installation Procedure for NEC Rack/Third Vendor's Rack

This server can be installed in either the NEC rack or a third vendor's rack. Take the following
procedure to install the server in the rack:
IMPORTANT:
instruction manual provided with the cable arm.
Preparation before Installation
The slide rail is fixed with the screw to prevent from falling off during transportation. Remove the
left and right core nuts from the front of the server before you install the server in the rack.
Hold the core nut, and rotate the set screw to remove the core nut.
Keep the removed core nuts for future use.
Removing the Rail Assemblies
Remove the sliding rails from the server.
Hold the rails and slowly slides them toward the rear of the server until a "click" is heard. The
click indicates that the rails are locked.
Push the release levers on the right and left sides of the server, and remove the rail assemblies from
the server while unlocking.
Release lever
When installing the optional cable arm, see the
Setting Up Your Server
Set screw
Core nut
3-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

N8100-1061fN8100-1062fN8100-1063f

Table of Contents