Installation Procedure for NEC Rack/Third Vendor's Rack

This server can be installed in either the NEC rack or a third vendor's rack. Take the following
procedure to install the server in the rack:
IMPORTANT:
instruction manual provided with the cable arm.
Preparation before Installation
The slide rail is fixed with the screw to prevent from falling off during transportation. Remove the
left and right cage nuts from the front of the server before you install the server in the rack.
Hold the cage nut, and rotate the set screw to remove the cage nut.
Keep the removed cage nuts for future use.
Removing the Rail Assemblies
Remove the sliding rails from the server.
Hold the rails and slowly slides them toward the rear of the server until a "click" is heard. The click
indicates that the rails are locked.
Push the release levers on the right and left sides of the server, and remove the rail assemblies from
the server while unlocking.
Release lever
When installing the optional cable arm, see the
Setting Up Your Server 3-7
Setscrew
Cage nut