PID Loop Operation

In standard operation, the inverter uses a reference source selected by parameter A001
for the output frequency, which may be a fixed value (F001), a variable set by the front
panel potentiometer, or value from an analog input (voltage or current). To enable PID
operation, set A071 = 01. This causes the inverter to calculate the target frequency, or
setpoint.
A calculated target frequency can have a lot of advantages. It lets the inverter adjust the
motor speed to optimize some other process of interest, potentially saving energy as
well. Refer to the figure below. The motor acts upon the external process. To control that
external process, the inverter must monitor the process variable. This requires wiring a
sensor to either the analog input terminal [O] (voltage) or terminal [OI] (current).
Setpoint
SP
PV
When enabled, the PID loop calculates the ideal output frequency to minimize the loop
error. This means we no longer command the inverter to run at a particular frequency, but
we specify the ideal value for the process variable. That ideal value is called the setpoint,
and is specified in the units of the external process variable. For a pump application it
may be gallons/minute, or it could be air velocity or temperature for an HVAC unit.
Parameter A075 is a scale factor that relates the external process variable units to motor
frequency. The figure below is a more detailed diagram of the PID function.
Standard
setting
F001
Multi-speed
settings
A020
to
A035
Potentiometer
on keypad
V/I input
select
[AT]
Voltage
O
A GND
L
OI
Current
Error
PID
Freq.
Calculation
Setpoint
(Target)
Scale factor
Frequency
reciprocal
source select
1
A001
A075
Process Variable
(Feedback)
Analog input scaling
A012
A011
A015 A013 A014
A076
PID V/I input select
SJ200
Inverter
Motor
Process Variable (PV)
Scale factor
A075
P gain
A072
Error
SP
I gain
A073
PV
D gain
A074
Scale factor
PV
A075
4–57
Inverter
2
External
Process
Sensor
F001
Frequency
setting
Monitor
D004