"B" Group: Fine Tuning Functions
Func.
Code
SRW Display
B021 Overload restriction
operation mode
OL Mode
B221 Overload restriction
operation mode, 2nd
motor
2OL Mode
B022 Overload restriction
setting / input monitor
OL LVL
B222 Overload restriction
setting / input monitor,
2nd motor
2OL LVL
B023 Deceleration rate at
overload restriction
2OL Cnst 0001.0s
B223 Deceleration rate at
overload restriction,
2nd motor
OL Cnst
B028 Overload restriction
source selection
OL L-Slct
B228 Overload restriction
source selection, 2nd
motor
2OL L-Slct
"B" Function
Name /
Select the operating mode
during overload conditions,
three options, option codes:
ON
00... Disabled
01... Enabled for acceleration
and constant speed
02... Enabled for constant
speed only
ON
Sets the level for overload
restriction, between 10% and
150% of the rated current of
002.40A
the inverter, setting resolution
is 1% of rated current. This
parameter monitors (read-only)
the [O]–[L] input when that
input is the overload restriction
002.40A
source (B028/B228 = 01).
Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution is 0.1.
Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution is 0.1.
0001.0s
Two options; select codes:
00... B022/B222 setting level
01... [O]–[L] analog input
C022
Two options; select codes:
00... B022/B222 setting level
01... [O]–[L] analog input
C022
Run
Mode
Edit
Description
Lo Hi
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
Defaults
–FE(F)
–FU
Units
(EU)
(USA)
01
01
01
01
Rated current x
A
1.5
Rated current x
A
1.5
1.0
30.0
sec.
1.0
30.0
sec.
00
00
00
00

Advertisement