Troubleshooting Tips - Hitachi SJ2002 Series Instruction Manual

Hide thumbs Also See for SJ2002 Series:
Table of Contents

Advertisement

Troubleshooting Tips

The table below lists typical symptoms and the corresponding solution(s).
Symptom/condition
The inverter
outputs [U], [V],
[W] are not
supplying
voltage.
The motor
will not run.
Inverter outputs
[U], [V], [W]
are supplying
voltage.
The optional
remote operator
is used (SRW).
The direction of the motor is
reversed.
Probable Cause
Is the frequency command source
A001 parameter setting correct?
Is the Run command source A002
parameter setting correct?
Is power being supplied to termi-
nals [L1], [L2], and [L3/N]? If so,
the POWER lamp should be ON.
Is there an error code
E X X
displayed?
Are the signals to the intelligent
input terminals correct?
Is the Run Command active?
Is the [FW] terminal (or [RV])
connected to [PCS] (via switch,
etc.)
Has the frequency setting for F001
been set greater than zero?
Are the control circuit terminals
[H], [O], and [L] connected to the
potentiometer?
Is the RS (reset) function or FRS
(free-run stop) function ON?
Is the motor load too heavy?
Are the operational settings
between the remote operator and
the inverter unit correct?
Are the connections of output
terminals [U/T1], [V/T2], and
[W/T3] correct?
Is the phase sequence of the motor
forward or reverse with respect to
[U/T1], [V/T2], and [W/T3]?
Are the control terminals [FW] and
[RV] wired correctly?
Is parameter F004 properly set?
SJ200
Inverter
2
Solution
Make sure the parameter
setting A001 is correct.
Make sure the parameter
setting A002 is correct.
Check terminals [L1], [L2],
and [L3/N], then [U/T1],
[V/T2], and [W/T3].
Turn ON the power supply
or check fuses.
Press the Func. key and
determine the error type.
Eliminate the error cause,
then clear the error (Reset).
Verify the terminal functions
for C001 – C006 are correct.
Turn ON Run Command
enable.
Supply 24V to [FW] or [RV]
terminal, if configured.
Set the parameter for F001
to a safe, non-zero value.
If the potentiometer is the
frequency setting source,
verify voltage at [O] > 0V.
Turn OFF the command(s).
Reduce load, and test the
motor independently.
Check the operator type
setting.
Make connections according
to the phase sequence of the
motor. In general:
FWD = U-V-W, and
REV=U-W-V.
Use terminal [FW] for
forward, and [RV] for
reverse.
Set motor direction in F004.
6–3