Hitachi SJ2002 Series Instruction Manual page 249

Hide thumbs Also See for SJ2002 Series:
Table of Contents

Advertisement

• When a read coil is outside the defined coils, the final coil data to be transmitted
contains "0"as the status of the coil outside the range.
• When the Read Coil Status command cannot be executed normally, see the exception
response.
Read Holding Register [03h]:
This function reads the contents of the specified number of consecutive holding registers
(of specified register addresses). An example follows below.
• Reading previous three trip factors from an inverter having a slave address "5"
• This example assumes the previous three trip factors are as follows:
SJ200
Command
2
Coil Number
Trip factor
Over-voltage (E07)
Query:
No.
Field Name
1
Slave address *1
2
Function code
3
Register start number
(high order)
4
Register start number
(low order)
5
Number of holding
registers (high order)
6
Number of holding
registers (low order)
7
CRC-16 (high order)
8
CRC-16 (low order)
Note 1:
Broadcasting is disabled.
D081 (N)
D082 (N-1)
0019h
Under-voltage (E09)
Response:
Example
No.
(Hex)
05
1
03
2
00
3
4
19
5
00
6
03
7
D5
88
8
9
10
11
Note 2:
SJ200
Inverter
2
D083 (N-2)
001Ah
0018h
No trip
Field Name
Slave address
Function code
Data size (in bytes) *2
Register start number
(high order)
Register start number
(low order)
Register start number + 1
(high order)
Register start number +1
(low order)
Register start number + 2
(high order)
Register start number +2
(low order)
CRC-16 (high order)
CRC-16 (low order)
Data is transferred by the
specified number of data bytes
(data size). In this case, 6 bytes
are used to return the content
of three holding registers.
B–11
Example
(Hex)
05
03
06
00
07
00
09
00
FF
36
37