If the Potentiometer Enable LED is OFF, follow the steps below.
Action
(Starting point)
key.
Press the
FUNC.
key again.
Press the
FUNC.
key.
Press the
2
key.
Press the
STR
Select the Keypad for the RUN Command - The RUN
command causes the inverter to accelerate the motor to
the selected speed. The Run command can arrive from
various sources, including the control terminals, the Run
key on the keypad, or the network. In the figure to the
right, notice the Run Key Enable LED, just above the
Run key. If the LED is ON, the Run key is already
selected as the source, and you may skip this step. Note
that the default setting depends on the country.
If the Potentiometer Enable LED is OFF, follow the steps below (the table resumes
action from the end of the previous table).
Action
(Starting point)
key once.
Press the
1
key.
Press the
FUNC.
key.
Press the
1
key.
Press the
STR
NOTE: After completing the steps above, the Run Key Enable LED will be ON. This
does not mean the motor is trying to run; it means that the RUN key is now enabled.
DO NOT press the RUN key at this time—complete the parameter setup first.
SJ200
Display
Func./Parameter
"A" Group selected
A – – –
Speed command source setting
A 0 0 1
00 = Keypad potentiometer
0 1
01 = Control terminals
02 = Function F001 setting
03 = ModBus network
10 = Calculate function output
00 = potentiometer (selected)
0 0
Stores parameter, returns to "A"
A 0 0 1
Group list
Run Key Enable LED
RUN
FUNC.
Display
Func./Parameter
Speed command source setting
A 0 0 1
Run command source setting
A 0 0 2
01 = control terminals
0 1
02 = Run key on keypad
03 = ModBus network input
02 = keypad (selected)
0 2
Stores parameter, returns to "A"
A 0 0 2
Group list
2–29
Inverter
2
POWER
HITACHI
ALARM
5 0.0
Hz
A
RUN
STOP
PRG
RESET
2
1
STR