Prepare for Wiring
Step 5: It is very important to perform the wiring steps carefully and correctly. Before
5
proceeding, please study the caution and warning messages below.
WARNING: "Use 60/75°C Cu wire only" or equivalent.
WARNING: "Open Type Equipment."
WARNING: "Suitable for use on a circuit capable of delivering not more than 100,000
rms symmetrical amperes, 240 V maximum." For models with suffix N or L.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100,000
rms symmetrical amperes, 480 V maximum." For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric
shock and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel. Other-
wise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF. Oth-
erwise, you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter or operate an inverter that is
not mounted according the instructions given in this manual. Otherwise, there is a danger
of electric shock and/or injury to personnel.