Hitachi SJ2002 Series Instruction Manual page 120

Hide thumbs Also See for SJ2002 Series:
Table of Contents

Advertisement

3–40
"B" Group: Fine Tuning Functions
Func.
Code
SRW Display
B080 [AM] analog signal
gain
AM-Adj
B082 Start frequency adjust-
ment
fmin
B083 Carrier frequency
setting
Carrier
B084 Initialization mode
(parameters or trip
history)
INIT Mode
B085 Country code for initial-
ization
INIT Slct
B086 Frequency scaling
conversion factor
Cnv Gain
B087 STOP key enable
STP Key
"B" Function
Name /
Adjust of analog output at
terminal [AM],
range is 0 to 255
00100%
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
0000.5Hz
Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz
0005.0
Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
TRP
02... Trip history clear and
parameter initialization
Select default parameter values
for country on initialization,
four options, option codes:
USA
00... Japan version
01... Europe version
02... US version
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
0001.0
Select whether the STOP key
on the keypad is enabled, two
ON
option codes:
00... enabled
01... disabled
Run
Mode
Edit
Description
Lo Hi
✔ ✔
✘ ✔
✘ ✘
✘ ✘
✘ ✘
✔ ✔
✘ ✔
Defaults
–FE(F)
–FU
Units
(EU)
(USA)
100.
100.
0.5
0.5
Hz
5.0
5.0
kHz
00
00
01
02
1.0
1.0
00
00

Advertisement

Table of Contents
loading

Table of Contents