When writing in a selected coil fails, see the exception response.
Write in Holding Register [06h]:
This function writes data in a specified holding register. An example follows:
• Write "50Hz" as the first Multi-speed 0 (A020) in an inverter having slave address
"5."
• This example uses change data "500(1F4h)" to set "50Hz" as the data resolution of the
register "003Ah" holding the first Multi-speed 0 (A020) is 0.1Hz
Query:
No.
Field Name
1
Slave address *1
2
Function code
3
Register start number
(high order)
4
Register start number
(low order)
5
Change data
(high order)
6
Change data
(low order)
7
CRC-16 (high order)
8
CRC-16 (low order)
Note 1:
No response is made for a
broadcasting query.
When writing in a selected holding register fails, see the exception response.
Response:
Example
No.
(Hex)
05
1
Slave address
06
2
Function code
00
3
Register start
number (high order)
3A
4
Register start
number (low order)
01
5
Change data
(high order)
F4
6
Change data
(low order)
A8
7
CRC-16 (high order)
54
8
CRC-16 (low order)
SJ200
Inverter
2
Example
Field Name
(Hex)
05
06
00
3A
01
F4
A8
54
B–13