Hitachi SJ2002 Series Instruction Manual page 174

Hide thumbs Also See for SJ2002 Series:
Table of Contents

Advertisement

4–32
Using Intelligent Input Terminals
Force Operation from Digital Operator
This function permits a digital operator interface to override the following two settings
in the inverter:
• A001 - Frequency source setting
• A002 - Run command source setting
When using the [OPE] terminal input, typically A001 and A002 are configured for
sources other than the digital operator interface for the output frequency and Run
command sources, respectively. When the [OPE] input is ON, then user has immediate
command of the inverter, to start or stop the motor and to set the speed.
Option
Terminal
Code
Symbol
31
OPE
Valid for inputs:
Required settings:
Notes:
When changing the [OPE] state during Run Mode
(inverter is driving the motor), the inverter will stop
the motor before the new [OPE] state takes effect.
If the [OPE] input turns ON and the digital operator
gives a Run command while the inverter is already
running, the inverter stops the motor. Then the
digital operator can control the motor.
Input
Function Name
State
Force Operation
ON
from Digital
Operator
OFF
C001, C002, C003, C004,
C005, C006
A001 (set not equal to 00)
A002 (set not equal to 02)
Description
Forces the operator interface to override:
A001 - Frequency Source Setting, and
A002 - Run Command Source Setting
Parameters A001 and A002 are in effect again,
for the frequency source and the Run command
source, respectively
Example (requires input configuration—see
page 3–45):
OPE
L
6
5
4
See I/O specs on page 4–6.
3
2
1
PCS

Advertisement

Table of Contents
loading

Table of Contents