B–58
ModBus Data Listing
Func. Code
B088
— Restart mode after FRS
—
(Reserved)
B090
— Dynamic braking usage
ratio
B091
— Stop mode selection
B092
— Cooling fan control
—
(Reserved)
—
(Reserved)
B095
— Dynamic braking control
B096
— Dynamic braking activa-
tion level
—
(Reserved)
B098
— Thermistor for thermal
protection control
B099
— Thermal protection level
setting
B100
— Free-setting V/f freq. (1)
B101
— Free-setting V/f voltage (1)
B102
— Free-setting V/f freq. (2)
B103
— Free-setting V/f voltage (2)
B104
— Free-setting V/f freq. (3)
B105
— Free-setting V/f voltage (3)
B106
— Free-setting V/f freq. (4)
B107
— Free-setting V/f voltage (4)
B108
— Free-setting V/f freq. (5)
B109
— Free-setting V/f voltage (5)
B110
— Free-setting V/f freq. (6)
B111
— Free-setting V/f voltage (6)
B112
— Free-setting V/f freq. (7)
B113
— Free-setting V/f voltage (7)
Holding Registers, "B" Group Fine Tuning Functions
Name
R/W
R/W
00 . Restart from 0Hz
01 . Restart from frequency
detected from actual speed
of motor
02 . Restart from active matching
frequency
—
R/W
0.0 to 100.0 (%)
Set = 0.0 to disable dynamic
braking
R/W
00 . DEC (decelerate and stop)
01 . FRS (free run to stop)
R/W
00 . Fan always ON
01 . Fan ON during RUN,
OFF during STOP
—
—
R/W
00 . Disable
01 . Enable during RUN only
02 . Enable always
R/W
330 to 380 (V) (200V class),
660 to 760 (V) (400V class)
—
R/W
00 . Disable
01 . Enable-PTC thermistor
02 . Enable-NTC thermistor
R/W
Thermistor resistance threshold
at which trip occurs
R/W
0. to Free-setting V/f freq. (2)
R/W
0.0 to 800.0 (V)
R/W
0. to Free-setting V/f freq. (3)
R/W
0.0 to 800.0 (V)
R/W
0. to Free-setting V/f freq. (4)
R/W
0.0 to 800.0 (V)
R/W
0. to Free-setting V/f freq. (5)
R/W
0.0 to 800.0 (V)
R/W
0. to Free-setting V/f freq. (6)
R/W
0.0 to 800.0 (V)
R/W
0. to Free-setting V/f freq. (7)
R/W
0.0 to 800.0 (V)
R/W
0. to 400.0 (V)
R/W
0.0 to 800.0 (V)
Description
Register
hex
135Bh
—
135Ch
135Dh
135Eh
135Fh
—
1360h
—
1361h
1362h
1363h
—
1364h
1365h
1366h
1367h
1368h
1369h
136Ah
136Bh
136Ch
136Dh
136Eh
136Fh
1370h
1371h
1372h
1373h
1374h
Network Data
Range
Res.
dec.
04955
0, 1, 2
—
04956
—
—
04957
0 to 1000
0.1 %
04958
0, 1
—
04959
0, 1
—
04960
—
—
04961
—
—
04962
0, 1, 2
—
04963
330 to 380
1 V
660 to 760
04964
—
—
04965
0, 1, 2
—
1 Ω
04966
0 to 9999
04967
0 to V/f 2
1 Hz
04968
0 to 8000
0.1 V
04969
0 to V/f 3
1 Hz
04970
0 to 8000
0.1 V
04971
0 to V/f 4
1 Hz
04972
0 to 8000
0.1 V
04973
0 to V/f 5
1 Hz
04974
0 to 8000
0.1 V
04975
0 to V/f 6
1 Hz
04976
0 to 8000
0.1 V
04977
0 to V/f 7
1 Hz
04978
0 to 8000
0.1 V
04979
0 to V/f 8
1 Hz
04980
0 to 8000
0.1 V