Func. Code
Name
D084
— Trip monitor 4
D085
— Trip monitor 5
D086
— Trip monitor 6
D090
— Programming error
monitor
—
(Reserved)
Holding Registers, "D" Group Monitor Functions
R/W
Description
R
Factor code
R
Inverter status
R
Frequency (high)
R
Frequency (low)
R
Current
R
Voltage
R
Run time (high)
R
Run time (low)
R
ON time (high)
R
ON time (low)
R
Factor code
R
Inverter status
R
Frequency (high)
R
Frequency (low)
R
Current
R
Voltage
R
Run time (high)
R
Run time (low)
R
ON time (high)
R
ON time (low)
R
Factor code
R
Inverter status
R
Frequency (high)
R
Frequency (low)
R
Current
R
Voltage
R
Run time (high)
R
Run time (low)
R
ON time (high)
R
ON time (low)
R
Displays programming error
code
—
—
SJ700
Inverter
2
Network Data
Register
Range
hex
dec.
0030h
00048
(see codes in
next table)
0031h
00049
0032h
00050
0 to 40000
0033h
00051
0034h
00052
—
0035h
00053
—
0036h
00054
—
0037h
00055
0038h
00056
—
0039h
00057
003Ah
00058
(see codes in
next table)
003Bh
00059
003Ch
00060
0 to 40000
003Dh
00061
003Eh
00062
—
003Fh
00063
—
0040h
00064
—
0041h
00065
0042h
00066
—
0043h
00067
0044h
00068
(see codes in
next table)
0045h
00069
0046h
00070
0 to 40000
0047h
00071
0048h
00072
—
0049h
00073
—
004Ah
00074
—
004Bh
00075
004Ch
00076
—
004Dh
00077
004Eh
00078
Warning
code
004Fh
00079
—
to
to
08FFh
02303
B–39
Res.
—
—
0.01 Hz
0.1 A
1 V
1 hour
1 hour
—
—
0.01 Hz
0.1 A
1 V
1 hour
1 hour
—
—
0.01 Hz
0.1 A
1 V
1 hour
1 hour
—
—