Hitachi SJ7002 Series Instruction Manual page 119

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Suppose the electronic thermal setting (B012) is set to 44 Amperes. The left graph below shows
the effect of the free setting torque characteristic curve. For example, at (B017) Hz, the output
current level to cause overheating in a fixed time period is reduced by a factor of (B018). The
right graph below shows the reduced trip current levels in those conditions for given trip times.
Trip
time (s)
0.5
Any intelligent output terminal may be programmed to indicate a thermal warning [THM].
Parameter C061 determines the warning threshold. Please see
page 4–52
for more details.
Func.
Name/
Code
Description
B012
Level of electronic thermal setting
B212
Level of electronic thermal setting, 2nd motor
B312
Level of electronic thermal setting, 3rd motor
B013
Electronic thermal characteristic
B213
Electronic thermal characteristic,
2nd motor
B313
Electronic thermal characteristic,
3rd motor
B015
Free setting, electronic thermal frequency (1)
B016
Free setting, electronic thermal current (1)
B017
Free setting, electronic thermal frequency (2)
B018
Free setting, electronic thermal current (2)
B019
Free setting, electronic thermal frequency (3)
B020
Free setting, electronic thermal current (3)
60
0
(x)
(y)
Reduced trip current at (B017) Hz
Keypad
SRW
OPE
0.20 x rated current) to
(2.00 x rated current) (A)
0.20 x rated current) to
(2.00 x rated current) (A)
0.20 x rated current) to
(2.00 x rated current) (A)
00
SUB
Reduced torque
0 1
CRT
Constant torque
02
V/f free-setting
FREE
00
SUB
Reduced torque
0 1
CRT
Constant torque
02
FREE
V/f free-setting
00
SUB
Reduced torque
0 1
CRT
Constant torque
02
FREE
V/f free-setting
0.0 to 400.0 (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.0 to 1000. (A)
0.0 to 400.0 (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.0 to 1000. (A)
0.0 to 400.0 (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.0 to 1000. (A)
SJ700
(x) = B018 value x 116%
(y) = B018 value x 120%
(z) = B018 value x 150%
A
(z)
"Thermal Warning Signal" on
Range and Settings
FEF2
FE2
(EU)
rated current of inverter
rated current of inverter
rated current of inverter
01
01
01
0.
0.0
0.
0.0
0.
0.0
3–35
Inverter
2
Defaults
Run
Mode
FUF2
FF2
Edit
FU2
F2
Lo Hi
(USA)
(Jpn)
✘ ✔
✘ ✔
✘ ✔
✘ ✔
01
00
✘ ✔
01
00
✘ ✔
01
00
✘ ✔
0.
0.
✘ ✔
0.0
0.0
✘ ✔
0.
0.
✘ ✔
0.0
0.0
✘ ✔
0.
0.
✘ ✔
0.0
0.0