3–22
"A" Group: Standard Functions
PID Control
Func.
Name/
Code
Description
A071
PID Enable
A072
PID proportional gain
A073
PID integral time constant
A074
PID derivative time constant
A075
PV scale conversion
Process Variable (PV) scale factor (multiplier)
A076
PV source setting
Selects source of Process
Variable (PV)
A077
Reverse PID Action
Changes response to error
A078
PID output limit
A079
PID feed forward select
When enabled, the built-in PID loop calculates an ideal inverter output value to cause a loop
feedback process variable (PV) to move closer in value to the setpoint (SP). The current
frequency command serves as the SP. The PID loop algorithm will read the analog input for the
process variable (you specify either current or voltage input) and calculate the output.
• A scale factor in A075 lets you multiply the PV by a factor, converting it into engineering
units for the process.
• Proportional, integral, and derivative gains are all adjustable.
• Optional – You can assign an intelligent input terminal the option code 23, PID Disable.
When active, this input disables PID operation. See
on page
3–51.
• See
"PID Loop Operation" on page 4–75
Keypad
SRW
OPE
00
OFF
PID operation OFF
0 1
ON
PID operation ON
02
R-ON
PID operation ON with inverted output
0.2 to 5.0
0.0 to 999.9, 1000. to 3600. (seconds)
0.0 to 99.99, 100.0 (seconds)
0.01 to 99.99, 100.0 (seconds)
00
OI
[OI] terminal (current input)
0 1
O
[O] terminal (voltage input)
02
COM
Communication input
03
PLS
Pulse train frequency input
1 0
MATH
CALCULATE function output
00
OFF
PID input = SP – PV (normal)
0 1
ON
PID input = –(SP – PV) (reverse)
Range is 0.0 to 100.0
00
Disable
no
0 1
O
[O] terminal (voltage input)
02
OI
[OI] terminal (current input)
03
O2
[O2] terminal (voltage input)
NOTE: The setting A073 for the integrator is the integrator's time constant Ti, not the gain.
The integrator gain Ki = 1/Ti. When you set A073 = 0, the integrator is disabled.
"Intelligent Input Terminal Overview"
for more information.
Range and Settings
Defaults
Run
Mode
FEF2
FUF2
FF2
Edit
FE2
FU2
F2
Lo Hi
(EU)
(USA)
(Jpn)
✘ ✔
00
00
00
✘ ✔
✘ ✔
✔ ✔
1.0
1.0
1.0
✔ ✔
1.0
1.0
1.0
✔ ✔
0.0
0.0
0.0
✘ ✔
1.00
1.00
1.00
✘ ✔
✘ ✔
00
00
00
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
00
00
00
✘ ✔
✘ ✔
0.00
0.00
0.00
✘ ✔
00
00
00
✘ ✔
✘ ✔
✘ ✔

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents