Trip History and
We recommend that you first find the cause of the fault before attempting clearing it. When a
fault occurs, the inverter stores important performance data at the moment of the fault. To

Inverter Status

access the data, use the monitor functions (Dxxx) and select D081 for details about the present
fault (E
shifts D081–D085 to D082–D086, and writes the new error to D081.
The following Monitor Menu map shows how to access the error codes. When fault(s) exist,
you can review their details by first selecting the proper function: D081 is most recent, and
D086 is the oldest.
). The previous five faults are stored in D081 to D086, with D (E
n
2
1
d08 1
Error
exists?
Yes
E07.2
1
60.00
1
4.00
1
270.0
1
15
1
18
1
Monitor Menu
Trip History
2
2
d086
1
d082
FUNC.
No error
FUNC.
No
Current Trip
Conditions
Error Code
Output frequency at
trip point
Motor current at
trip point
DC bus voltage at
trip point
Cumulative inverter
operation time
at trip point
Cumulative power-
ON time at trip point
FUNC.
6–15
SJ700
Inverter
2
to E
). Each error
n-1
n-5
2