Hitachi SJ7002 Series Instruction Manual page 137

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Option
Terminal
Function Name
Code
Symbol
29
UDC
Remote Control Data
Clearing
31
OPE
Operator Control
32
SF1
Multi-speed bit 1
33
SF2
Multi-speed bit 2
34
SF3
Multi-speed bit 3
35
SF4
Multi-speed bit 4
36
SF5
Multi-speed bit 5
37
SF6
Multi-speed bit 6
38
SF7
Multi-speed bit 7
39
OLR
Overload restriction
40
TL
Torque limit enable
41
TRQ1
Torque limit selection, bit
1
42
TRQ2
Torque limit selection, bit
2
43
PPI
Proportional /
Proportional/Integral
mode selection
44
BOK
Brake confirmation signal Indicates external brake has released (used only for external
45
ORT
Orientation (home search) The encoder is in the home (oriented) position
46
LAC
LAC: LAD cancel
47
PCLR
Position deviation reset
48
STAT
Pulse train position
command input enable
50
ADD
Add frequency enable
51
F-TM
Force terminal mode
52
ATR
Torque control enable
53
KHC
Clear cumulative power
value
54
SON
Speed servo ON
Input Function Summary Table
Clears the UP/DWN frequency memory by forcing it to equal
the set frequency parameter F001. Setting C101 must be
set=00 to enable this function to work.
Forces the source of the output frequency setting (A001) and
the RUN command (A002) to be from the digital operator
(F001 and the Run key, respectively)
Multiple speed select, Bit 1
Multiple speed select, Bit 2
Multiple speed select, Bit 3
Multiple speed select, Bit 4
Multiple speed select, Bit 5
Multiple speed select, Bit 6
Multiple speed select, Bit 7
Turn ON to select current overload parameter set 2
(B024, B025, B026); OFF selects set 1(B021, B022, B023)
ON enables torque limit feature; OFF disables all torque limit
sources and defaults to 200% of inverter rated torque output
Binary encoded torque limit select, Bit 1 (LSB)
Binary encoded torque limit select, Bit 2 (MSB)
ON selects Proportional-only control; OFF selects Propor-
tional-Integral control
brake control function)
Disables the normal Linear Accel / Decel (LAD) mode
Clears the position deviation by setting the actual position
equal to the desired position
Enables the pulse train control of motor
Adds the A145 value (Add Frequency) to the output
frequency
Force inverter to use input terminals for output frequency and
Run command sources
Inverter operates by controlling torque instead of speed
Clears cumulative power data displayed by parameter D015
Enables the inverter to accept FW/REV commands; for use
with V/F curve vector control with sensor (A044=05)
SJ700
Inverter
2
Description