Exception Response:
When sending a query (excluding a broadcasting query) to an inverter, the master always
requests a response from the inverter. Usually, the inverter returns a response according to the
query. However, when finding an error in the query, the inverter returns an exception response.
The exception response consists of the fields shown below.
Field Configuration
Slave address
Function code
Exception code
CRC–16
The content of each field is explained below. The function code of the exception response is the
sum of the function code of the query and 80h. The exception code indicates the factor of the
exception response.
Function Code
Query
Exception Response
0 1 h
0 3 h
0 5 h
0 6 h
0 F h
1 0 h
Exception Code
0 1 h
The specified function is not supported.
0 2 h
The specified address is not found.
0 3 h
The format of the specified data is not acceptable.
2 1 h
The data to be written in a holding register is outside the inverter.
2 2 h
The specified functions are not available to the inverter.
• Function to change the content of a register that cannot be changed
while the inverter is in service
Function to submit an ENTER command during running (UV)
Function to write in a register during tripping (UV)
Function to write in a read-only register (or coil)
8 1 h
8 3 h
8 5 h
8 6 h
8 F h
9 0 h
Description
B–31
SJ700
Inverter
2