3–38
"B" Group: Fine-Tuning Functions
Software Lock
Mode
Func.
Name/
Code
Description
B031
Software lock mode
selection
The software lock function keeps personnel from accidentally changing parameters in the
inverter memory. Use B031 to select from various protection levels.
The table below lists all combinations of B031 option codes and the
ON/OFF state of the [SFT] input. Each Check ✔ or Ex ✘ indicates
whether the corresponding parameter(s) can be edited. The Standard
Parameters column below lists Low and High level access for some
lock modes. These refer to the parameter tables throughout this
chapter, each of which includes a column titled Run Mode Edit as
shown to the right. The two marks (Check ✔ or Ex ✘) under the "Lo
Hi" subtitle indicate whether Low-level and/or High-level access
applies to each parameter as defined in the table below. In some lock modes, you can edit only
F001 and the Multi-speed parameter group that includes A020, A220, A320, A021–A035, and
A038 (Jog). However, it does not include A019, Multi-speed operation selection. The editing
access to B031 itself is unique, and is specified in the right-most two columns below.
[SFT]
B031 Lock
Intelligent
Mode
Input
00
OFF
ON
01
OFF
ON
02
(ignored)
03
(ignored)
10
(ignored)
NOTE: Since the software lock function B031 is always accessible when the motor is stopped,
this feature is not the same as password protection used in other industrial control devices.
Keypad
SRW OPE
00
MD0
Low-level access, [SFT] input blocks all edits
0 1
MD1
Low-level access, [SFT] input blocks edits
(except F001 and Multi-speed parameters)
02
MD2
No access to edits
03
MD3
No access to edits except F001 and Multi-speed
parameters
10
MD10
High-level access, including B031
NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the [SFT]
function to one of the intelligent input terminals. See
F001 and
Standard Parameters
Multi-speed
Stop
Run
Stop or Run
Low-level
Low-level
High-level
Range and Settings
"Software Lock" on page
Run
Mode
Edit
Lo Hi
✘ ✔
B031
Stop
Run
Defaults
Run
Mode
FEF2
FUF2
FF2
Edit
FE2
FU2
F2
Lo Hi
(EU)
(USA)
(Jpn)
✘ ✔
01
01
01
4–23.