Hitachi SJ7002 Series Instruction Manual page 31

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

The 400V models from –1850 to –4000HFU2/HFE2 (250 to 525 HP) include a DC reactor and
ferrite core.
Item
SJ700
inverters,
U.S. version
2
400V models
European ver.
Applicable motor size *2
Rated capacity, kVA, 400 / 480V
Rated input voltage
Rated input current (A)
Rated output voltage *3
Rated output current (A)
Overload capacity, output current (A)
Inv. efficiency at 100% rated output, %
Inverter Watt loss,
at 70% output
approximate (W)
at 100% output
DCL efficiency at 100% rated output, %
DCL Watt loss,
at 70% output
approximate (kW)
at 100% output
Dynamic braking
w/o braking unit
approx. % torque,
with braking unit
short time stop *7
DC braking
Electrical filtering
Weight
kg / lb
Footnotes for the preceding tables and the table that follows:
Note 1: The protection method conforms to JEM 1030.
Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using
Note 3: The output voltage decreases as the main supply voltage decreases (except when
Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for the
Note 5: When SLV is selected, please set the carrier frequency higher than 2.1 kHz.
Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor (when
Note 7: The braking torque via capacitive feedback is the average deceleration torque at the
Note 8: The frequency command will equal the maximum frequency at 9.8V for input voltage
Note 9: The storage temperature refers to the short-term temperature during transport.
Note 10: Conforms to the test method specified in JIS C0050 (1999). For the model types
Note 11: NEMA 1 applies up to 22kW. An optional wire-entry conduit box is required for
900HFU2
1100HFU2
9000HFE2
1100HFE2
HP
125
150
kW
90
110
121.9/146.3
150.3/180.4
3-phase (3-wire) 380 to 480V +10/-15%, 50/60 Hz ±5%
194
239
3-phase (3-wire): 380 to 480V (corresponding to input voltage)
176
217
50% for 60 sec., 200% for 0.5 sec.
95.2
95.2
3375
3900
4800
5550
8%
8%
Refer to separate DB Unit instruction manual or contact your Hitachi distributor
Variable operating frequency, time, and braking force
Built-in EMC filter and zero-phase reactor
55 / 121
55 / 121
other motors, care must be taken to prevent the rated motor current (50/60 Hz) from
exceeding the rated output current of the inverter.
using the AVR function). In any case, the output voltage cannot exceed the input
power supply voltage.
maximum allowable rotation speed.
selecting sensorless vector control—SLV).
shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous
regenerative braking torque. The average decel torque varies with motor loss. This
value decreases when operating beyond 50 Hz. If a large regenerative torque is
required, the optional regenerative braking resistor should be used.
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not
satisfactory for your application, contact your Hitachi sales representative.
excluded in the standard specifications, contact your Hitachi sales representative.
0.4kW to 55kW models to meet NEMA 1 rating.
400V Class Specifications
1500HFU2
1850HFU2
1320HFE2
1850HFE2
200
250
150
185
180.1/216.1
256 / 308
286
389
260
370
50% for 60 sec., 180% for 0.5 sec.
95.2
96.5
4670
4700
6650
6700
99.9
0.1
0.2
8%
10%
External DC reactor and ferrite core
70 / 54
140 / 308
1–9
SJ700
Inverter
2
3150HFU2
4000HFU2
3150HFE2
4000HFE2
425
525
315
400
416 / 499
554 / 665
630
840
600
800
96.2
96.3
8000
10500
11500
15000
99.9
99.9
0.1
0.1
0.2
0.2
10%
10%
210 / 463
360 / 792

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents