Hitachi SJ7002 Series Instruction Manual page 143

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Option
Function Name
Code
05
Input power
06
Electronic thermal
overload
07
LAD frequency
09
Motor temperature
10
Heat sink temperature
13
General YA(1) analog
output
14
General YA(2) analog
output
Output Function
The following parameters work in
conjunction with the intelligent output
Adjustment
function, when configured. The
Parameters
overload level parameter (C041) sets the
motor current level at which the
overload signal [OL] turns ON. The
range of settings is from 0% to 200% of
the rated current for the inverter. This
function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are avail-
able on other functions).
The frequency arrival signal, [FA1] to
[FA5], is intended to indicate when the
inverter output has reached (arrived at)
the target frequency. You can adjust the
timing of the leading and trailing edges
of the signal via two parameters specific
to acceleration and deceleration ramps,
C042 and C043.
The Error for the PID loop is the magni-
tude (absolute value) of the difference
between the Setpoint (desired value)
and Process Variable (actual value). The
PID output deviation signal [OD]
(output terminal function option code
04) indicates when the error magnitude
has exceeded a magnitude you define.
C028 Setting for Terminal [AM]; C029 Setting for Terminal [AMI]
Rated input power
Percentage of electronic overload attained
Internal ramp generator frequency
Thermistor input temp. reading in PWM
format
Inverter heatsink temp. reading in PWM
format
Internal analog value from EZ-Sequence
Internal analog value from EZ-Sequence
Description
Motor
current
Overload
signal
1
0
Output
frequency
Arrival
signal
1
0
SP
PID Error
(PV-SP)
Deviation
Signal
1
0
SJ700
Inverter
2
Corresponding Signal
Range
0 to 200%
0 to 100%
0 to max. frequency in Hz
0 to 200°C
0 to 200°C
0 to 100% (output only from
terminal [AM])
0 to 100% (output only from
terminal [AMI])
C041
t
C042
C043
t
C044
t