B–56
ModBus Data Listing
Func. Code
B042
— Torque limit (2) (reverse-
regenerating in 4-quadrant
mode)
B043
— Torque limit (3) (reverse-
driving in 4-quadrant
mode)
B044
— Torque limit (4) (forward-
regenerating in 4-quadrant
mode)
B045
— Torque limit LADSTOP
enable
B046
— Reverse Run protection
enable
—
(Reserved)
B050
— Controller deceleration and
stop on power loss
B051
— DC bus voltage trigger
level during power loss
B052
— Over-voltage threshold
during power loss
B053
H Deceleration time setting
during power loss
B053
L
B054
— Initial output frequency
decrease during power loss
B055
— Proportional gain setting
for non-stop operation at
power loss
B056
— Integral time setting for
non-stop operation at
power loss
—
(Reserved)
B060
— [O] input max. limit level
of window comparator
B061
— [O] input min. limit level
of window comparator
B062
— [O] input hysteresis width
of window comparator
B063
— [OI] input max. limit level
of window comparator
Holding Registers, "B" Group Fine Tuning Functions
Name
R/W
R/W
0. to 200. (%), no (disable torque
limit)
R/W
0. to 200. (%), no (disable torque
limit)
R/W
0. to 200. (%), no (disable torque
limit)
R/W
00 . Disable
01 . Enable
R/W
00 . Disable
01 . Enable
—
R/W
00 . Disable
01 . Constant decel to stop
02 . Constant DC voltage
control with resume
03 . Constant DC voltage
control
R/W
Sets trigger for controlled decel-
eration and stop on power loss
function
R/W
Sets over-voltage threshold for
controlled deceleration function
R/W
0.01 to 99.99, 100.0 to 999.9,
1000 to 3600 (seconds)
R/W
R/W
Sets the initial decrease in output
frequency upon power loss
R/W
0.00 to 2.55
R/W
0.0 to 9.999, 10.00 to 65.55
—
R/W
0. to 100. (%)
Lower limit = B061 + B062 / 2
R/W
0. to 100. (%)
Lower limit = B060 – B062 / 2
R/W
0. to 10. (%)
Lower limit = B061 – B062 / 2
R/W
0. to 100. (%)
Lower limit = B064 + B066 / 2
Description
Register
hex
132Ch
132Dh
132Eh
132Fh
1330h
—
1331h
to
1333h
1334h
1335h
1336h
1337h
1338h
1339h
133Ah
133Bh
—
133Ch
to
133Eh
133Fh
1340h
1341h
1342h
Network Data
Range
Res.
dec.
04908
0 to 200,
1 %
255= (no)
04909
0 to 200,
1 %
255= (no)
04910
0 to 200,
1 %
255= (no)
04911
0, 1
—
04912
0, 1
—
04913
—
—
to
04915
04916
0 to 3
—
04917
0 to 10000
0.1 V
04918
0 to 10000
0.1 V
04919
0 to
0.01 sec.
360000
04920
04921
0 to 1000
0.01 Hz
04922
0 to 255
0.01
04923
0 to 65535
0.001
sec.
04924
—
—
to
04926
04927
0 to 100
1 %
04928
0 to 100
1 %
04929
0 to 10
1 %
04930
0 to 100
1 %