3–50

"C" Group: Intelligent Terminal Functions

"C" Group: Intelligent Terminal Functions

Input Terminal
Configuration
Func.
Code
C001
C002
C003
C004
C005
C006
C007
C008
Func.
Code
C011
C012
C013
C014
The eight input terminals [1], [2], [3], [4], [5], [6], [7], and [8] can be configured for any of 44
different functions. The next two tables show how to configure the eight terminals. The inputs
are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1.
The inverter comes with default options for the eight terminals. These default settings are
initially unique, each one having its own setting. Note that European and US versions have
different default settings. You can use any option on any terminal, and even use the same option
twice to create a logical OR (though usually not required).
Functions and Options –The function codes in the following table let you assign one of 44
options to any of the eight logic inputs for the SJ700
C008 configure the terminals [1] through [8] respectively. The "value" of these particular
parameters is not a scalar value, but it is a discrete number that selects one option from many
available options.
For example, if you set function C001=01, you have assigned option 01 (Reverse Run) to
terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.
Name/
Description
Terminal [1] function
Terminal [2] function
Terminal [3] function
Terminal [4] function
Terminal [5] function
Terminal [6] function
Terminal [7] function
Terminal [8] function
The input logic convention is programmable for each of the six inputs. Most inputs default to
normally open (active high), but you can select normally closed (active low) in order to invert
the sense of the logic.
Name/
Description
SRW OPE
Terminal [1] active state
NO
NC
Terminal [2] active state
NO
NC
Terminal [3] active state
NO
NC
Terminal [4] active state
NO
NC
2
Range and Settings
63 programmable functions
available for terminals (see
next section)
Keypad
Range and Settings
00
Normally open (N.O.)
0 1
Normally closed (N.C.)
00
Normally open (N.O.)
0 1
Normally closed (N.C.)
00
Normally open (N.O.)
0 1
Normally closed (N.C.)
00
Normally open (N.O.)
0 1
Normally closed (N.C.)
inverters. The functions C001 through
Defaults
FEF2
FUF2
FF2
FE2
FU2
F2
(EU)
(USA)
(Jpn)
18 [RS]
18 [RS]
18 [RS]
16 [AT]
16 [AT]
16 [AT]
06 [JG]
06 [JG]
06 [JG]
11 [FRS] 11 [FRS] 11 [FRS]
09 [2CH] 09 [2CH] 09 [2CH]
03 [CF2] 13 [USP] 03 [CF2]
02 [CF1]
02 [CF1]
02 [CF1]
01 [RV]
01 [RV]
01 [RV]
Defaults
FEF2
FUF2
FF2
FE2
FU2
F2
(EU)
(USA)
(Jpn)
00
00
00
00
00
00
00
00
Run
Mode
Edit
Lo Hi
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
Run
Mode
Edit
Lo Hi
✘ ✔
00
✘ ✔
✘ ✔
00
✘ ✔
✘ ✔
00
✘ ✔
✘ ✔
00
✘ ✔