Negative Pulse Coil - Toshiba PROSEC T1-16S User Manual

Programmable controller basic hardware and function
Hide thumbs Also See for PROSEC T1-16S:
Table of Contents

Advertisement

7. Instructions

Negative pulse coil

( N )
Expression
A
Input
(
)
N
Function
When the input is changed form ON to OFF, the device A is set to ON for 1 scan time.
This instruction is used to detect the input changing from ON to OFF.
Execution condition
Input
OFF
When the input at last scan is OFF, sets A to OFF
When the input at last scan is ON, sets A to ON
ON
Sets device A to OFF
Operand
Name
X
A Device
Example
R101 comes ON for only 1 scan when X000 is changed from ON to OFF.
X000
R100
Note
The maximum usable number in a program is 2048.
(