FUN 101
Expression
Input
[ A
B ]
Output
Function
When the input is ON, the data of A and the data of B are compared, and if A is less than or equal
to B, the output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
X
A Compared
data
B Reference
data
Example
When R00C is ON, the data of D0125 is compared with the constant data -100, and if the data
of D0125 is less than or equal to -100, R020 is turned ON.
If the data of D0125 is -150, the comparison result is true. Consequently, R020 is turned ON.
D0125
-150
If the data of D0125 is 0, the comparison result is false. Consequently, R020 is turned OFF.
D0125
0
Note
This instruction deals with the data as signed integer (-32768 to 32767).
Less than or equal
Operation
A
B
A
B
Device
Y
R
S
T.
C. XW YW RW SW T
Constant
Constant
Output
OFF
ON
OFF
Register
C
-100
-100
Basic Hardware and Function
7. Instructions
Constant Index
D
I
J
K
R020 is ON
R020 is OFF
6F3B0253