7. Instructions
FUN 108
U
Expression
Input
[ A U
B ]
Output
Function
When the input is ON, the data of A and the data of B are compared, and if A is greater than B, the
output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
X
A Compared
data
B Reference
data
Example
When R00C is ON, the data of D0125 is compared with the constant data 40000, and if the
data of D0125 is greater than 40000, R020 is turned ON.
If the data of D0125 is 52000, the comparison result is true. Consequently, R020 is turned ON.
D0125
52000
If the data of D0125 is 21000, the comparison result is false. Consequently, R020 is turned
OFF.
D0125
21000
Note
This instruction deals with the data as unsigned integer (0 to 65535).
190
T1-16S User's Manual
Unsigned greater than
Operation
A
B
A
B
Device
Y
R
S
T.
C. XW YW RW SW T
Constant 40000
Constant 40000
Output
OFF
ON
OFF
Register
C
D
I
J
R020 is ON
R020 is OFF
6F3B0253
Constant Index