7. Instructions
Data table:
Register
D2000 #0 Operating frequency
D2001 #0 Output terminal status
D2002 #0 Frequency reference
D2003 #0 Operation command
D2004 #1 Operating frequency
D2005 #1 Output terminal status
D2006 #1 Frequency reference
D2007 #1 Operation command
D2020 #5 Operating frequency
D2021 #5 Output terminal status
D2022 #5 Frequency reference
D2023 #5 Operation command
The data format for the operating frequency and the frequency reference registers are 0.01 Hz units.
For example, if it is 60 Hz, the corresponding register data is 6000.
For the data format of the output terminal status register, refer to the Monitor mode (mode 1).
The bit assignment of the operation command register is as follows. For details, refer to your
Inverter manual.
F
E
D
C
Example operation:
To operate the #0 Inverter at 30 Hz forward rotation, write the value 3000 in D2002 and HC400 in
D2003. (HC400 = Bits F, E, A are 1, and others are 0)
The current operating frequency and the output terminal status of the #0 Inverter are stored in D2000
and D2001 respectively.
248
T1-16S User's Manual
Data contents
B
A
9
8
7
6
5
4
Signal direction
Read
Read
Write
Write
Read
Read
Write
Write
Read
Read
Write
Write
3
2
1
0
Programmed speed selection
0000 = None
0001 = Speed 1
0010 = Speed 2
:
1111 = Speed 15
PI operation (0 = Normal / 1 = Off)
DC braking (0 = Off / 1 = On)
Jog operation (0 = off / 1 = On)
F/R selection (0 = Forward / 1 = Reverse)
Run/Stop (0 = Stop / 1 = Run)
Free run (0 = Normal / 1 = Free run)
Emergency stop (0 = Normal / 1 = EMS)
Reset command (0 = Normal / 1 = Reset)
Frequency enable (0 = Disable / 1 = Enable)
Command enable (0 = Disable / 1 = Enable)