7. Instructions
< Write command mode (Mode 3) >
When the instruction input comes ON with the operand B+1 is 3, the Write command mode
(mode 3) is selected. In this mode, the T1-16S sends the user specified Write command to the
Inverter specified by the operand B, and repeats.
Sends the specified command with command data to #n Inverter
Repeat
Checks the acknowledge
The target Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command code and the command data setting registers are indirectly specified by the
operand A and A+1.
When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter.
Example
Data table designation
D1000
4
D1001
3010
When the data for each operand are set as above, the following operation condition is specified.
RW200=5
The target Inverter number is 5. Therefore T1-16S communicates with #5 Inverter.
D1000=4 & D1001=3010
specified as the command data setting register.
Data table:
Register
D3010 Command code
D3011 Command data
Example operation:
For example, to write the acceleration time parameter (10 seconds) to the #5 Inverter, set the
command code H0009 into D3010 and the value 100 into D3011.
For the command code and the command data format, refer to your Inverter manual.
252
T1-16S User's Manual
Parameter & status
RW200
RW201
RW202
RW203
Comm error code
RW204
RW205
RW206
RW207
D3010 is specified as the command code setting register and D3011 is
Data contents
5
3 (mode 3)
Execution status
Inverter comms
status map
Signal direction
Write
RS-485 port
D1010
H0030 (fixed)
D1011
0 (fixed)
6F3B0253