Toshiba PROSEC T1-16S User Manual page 103

Programmable controller basic hardware and function
Hide thumbs Also See for PROSEC T1-16S:
Table of Contents

Advertisement

Sampling trace function
The sampling trace function collects the status of specified devices or register at every
specified sampling timing. The collected data can be displayed on the programmer
(T-PDS) screen in the format of timing chart (for devices) or trend graph (for register).
The minimum sampling timing is the T1-16S's scan cycle.
This function is useful for program debugging and troubleshooting.
Sampling target
Devices (up to 8) and
Registers (up to 3)
Sampling capacity
256 times
The collected data is stored in the T1-16S internal buffer.
The buffer works as a ring buffer, and latest collected data can be displayed.
The sampling start/stop condition (arm condition) and the collection timing (trigger
condition) can be specified by status changing of devices.
For detailed key operations for arm/trigger conditions setting on the T-PDS, refer to
the manual for T-PDS.
T-PDS screen example of device timing chart
NOTE
(1) On the T-PDS, select '3 registers + 8 devices' as the sampling type.
(2) As the arm and trigger conditions, register values cannot be used.
(3) The After times setting is not effective for the T1-16S.
6. Programming Information
T1-16S
Basic Hardware and Function
6F3B0253
101