7. Instructions
FUN 185
7SEG
Expression
Input
[ A 7SEG B ]
Function
When the input is ON, this instruction converts the lower 4 bits data of A into the 7 segment code,
and stores it in B. The 7 segment code is normally used for a numeric display LED.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
X
A Source
B Destination
Example
When X000 is ON, the lower 4 bits data of RW15 is converted into the 7 segment code, and
the result is stored in lower 8 bits of RW10. 0 is stored in upper 8 bits of RW10.
For example, if RW15 is H0009, the corresponding 7 segment code H006F is stored in RW10.
F
E
D
RW15
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
Upper 12 bits are ignored
RW10
0 0 0 0 0 0 0 0 0 1 1 0 1 1 1 1
0 is stored in upper 8 bits
The 7 segment code conversion table is shown on the next page.
234
T1-16S User's Manual
7 segment decode
Output
Operation
Device
Y
R
S
T.
C. XW YW RW SW T
C
B
A
9
8
7
6
5
Output
OFF
ON
Register
C
4
3
2
1
0
(H0009)
7 segment decode
(H006F)
Constant Index
D
I
J
K
6F3B0253