8. Special I/O Functions

8.2 Variable input filter constant

Function
The input filter constant (ON/OFF delay time) of the leading 8 points X000 to X007
can be specified by user program within the range of 0 to 15ms. The default is 10ms.
The setting value is recognized at the first scan. Therefore, it cannot be changed after
the second scan.
Related registers
SW16
Function selection. Refer to section 8.1.
SW17
Operation
Input signal
Internal logic
Scan cycle
X device
Sample program
This program sets the input filter constant to 3ms.
260
T1-16S User's Manual
Input filter constant value
F E D C B A 9 8 7 6 5 4 3 2 1 0
No use (set to 0)
T
T: Input filter constant (0 to 15ms)
Setting value
0 to 15
T
T
6F3B0253
T