Programmable controller basic hardware and function
Hide thumbs Also See for PROSEC T1-16S:
Table of Contents

Advertisement

TON
ON delay timer
Expression
Input
[ A TON B ]
Function
When the input is changed from OFF to ON, timer updating for the timer register B is started. The
elapsed time is stored in B. When the specified time by A has elapsed after the input came ON, the
output and the timer device corresponding to B is turned ON. (Timer updating is stopped)
When the input is changed from ON to OFF, B is cleared to 0, and the output and the timer device
are turned OFF.
The available data range for operand A is 0 to 32767.
Execution condition
Input
OFF
No operation (timer is not updating)
ON
Elapsed time
Elapsed time
Operand
Name
X
A Preset time
B Elapsed time
Example
Y021 (and the timer device T.000) is turned ON 2 seconds after X000 came ON.
X000
Preset value
T000
T.000
Y021
Preset time (2s)
Output
Operation
preset time (timer is updating)
preset time (timer is not updating)
Device
Y
R
S
T.
C. XW YW RW SW T
Less than preset time
Output
OFF
OFF
ON
Register
C
D
I
J
Note
Time is set in 10 ms units for;
T1:
T000 to T031 (0 to 327.67 s)
T1S: T000 to T063 (0 to 327.67 s)
Time is set in 100 ms units for;
T1:
T032 to T063 (0 to 3276.7 s)
T1S: T064 to T255 (0 to 3276.7 s)
Multiple timer instructions (TON, TOF or
SS) with the same timer register are not
allowed.
Basic Hardware and Function
6F3B0253
7. Instructions
Constant Index
K
0 - 32767
129