Toshiba PROSEC T1-16S User Manual page 181

Programmable controller basic hardware and function
Hide thumbs Also See for PROSEC T1-16S:
Table of Contents

Advertisement

FUN 097
Expression
Input
[ A
B ]
Output
Function
When the input is ON, the data of A and the data of B are compared, and if A is greater than or
equal to B, the output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
X
A Compared
data
B Reference
data
Example
When R00C is ON, the data of D0125 is compared with the data of D0020, and if the data of
D0125 is greater than or equal to the data of D0020, R020 is turned ON.
If the data of D0125 is 3000 and that of D0020 is 3000, the comparison result is true.
Consequently, R020 is turned ON.
D0125
3000
If the data of D0125 is -1500 and that of D0020 is 0, the comparison result is false.
Consequently, R020 is turned OFF.
D0125
-1500
Note
This instruction deals with the data as signed integer (-32768 to 32767).
Greater than or equal
Operation
A
B
A
B
Device
Y
R
S
T.
C. XW YW RW SW T
D0020
D0020
Output
OFF
ON
OFF
Register
C
3000
0
Basic Hardware and Function
7. Instructions
Constant Index
D
I
J
K
R020 is ON
R020 is OFF
6F3B0253