Setup - Volume - Emerson Rosemount 3300 Series Reference Manual

Guided wave radar level and interface transmitters
Hide thumbs Also See for Rosemount 3300 Series:
Table of Contents

Advertisement

Rosemount 3300 Series

Setup - Volume

Figure 4-17. Setup Volume tab
4-22
Measurements Below Probe End
The Present Level=0... check box controls how the level value is presented
when the tank is almost empty. By selecting this check box the Level is set
equal to zero as long as the product surface is below the probe.
If the check box is not selected, the Level value is equal to the difference
between Reference Gauge Height R and Probe Length L when the product
surface is below the probe (see "Basic Configuration" on page 4-2 for
information on tank geometry).
The Volume tab lets you configure the transmitter for volume calculations.
You can choose one of the standard tank shapes or the strapping option.
Choose None if volume calculation is not used at all.
Choose one of the following options:
Vertical Cylinder
Horizontal Cylinder
Vertical Bullet
Horizontal Bullet
Sphere
Strap table
None
See Section 4: Volume Configuration for more information on Volume
configuration.
Reference Manual
00809-0100-4811, Rev CA
Level=0
Level=R-L
February 2006