Rosemount 3300 Series
Mechanical
Probes
Tensile strength
Collapse load
Sideway capacity
Material exposed to tank atmosphere
Dimensions
Probe angle
Housing / Enclosure
Flanges, Threads
Height above flange
Environment
Ambient temperature
Storage temperature
(3)
Process temperature
(3)
Process pressure
Humidity
Ingress protection
Telecommunication (FCC and R&TTE)
Factory sealed
Vibration resistance
Electromagnetic compatibility
Built-in Lightning Protection
Pressure Equipment Directive (PED)
Ordinary Location FM 3810,
Boiler Approval CSA B51-97
A-2
Coaxial: 1.3 ft (0.4 m) to 19.7 ft (6 m).
Rigid Twin Lead: 1.3 ft (0.4 m) to 9.8 ft (3 m).
Flexible Twin Lead: 3.3 ft (1 m) to 77.1 ft (23.5 m).
Rigid Single Lead: 1.3 ft (0.4 m) to 9.8 ft (3 m).
Flexible Single Lead: 3.3 ft (1 m) to 77.1 ft (23.5 m).
For further information see "Probe Selection Guide" on page 2-6.
Flexible Single Lead probe: 2698 lb (12 kN).
Flexible Twin Lead probe: 2023 lb (9 kN).
Flexible Single Lead probe: 3597 lb (16 kN).
Coaxial probe: 73.7 ft lbf, 3.7 lb at 19.7 ft (100 Nm, 1.67 kg at 6 m).
Rigid Twin Lead: 2.2 ft lbf, 0.22 lb at 9.8 ft (3 Nm, 0.1 kg at 3 m).
Rigid Single Lead: 4.4 ft lbf, 0.44 lb at 9.8 ft (6 Nm, 0.2 kg at 3 m).
• 316/316L SST (EN 1.4404), PTFE, PFA
®
• Hastelloy
C276 (UNS N10276), PTFE, PFA
®
• Monel
400 (UNS N04400), Teflon (PTFE, PFA) and O-ring materials (model code 3)
(2)
• PTFE
(model code 7)
(2)
• PTFE
, 316L SST (EN 1.4404) and O-ring materials (model code 8)
• 316L SST (EN 1.4404), Ceramics (Al2O3), Graphite, (HTHP probe, model code H)
• 316L SST (EN 1.4404), Ceramics (Al2O3), Graphite, PFA (HP probe, model code P)
(See "Ordering Information" on page A-12).
See "Dimensional drawings" on page A-7.
0 to 90 degrees from vertical axis.
Polyurethane-covered Aluminium.
See "Ordering Information" on page A-12.
See "Dimensional drawings" on page A-7.
-40 °F to +185 °F ( -40 °C to +85 °C), depends on approval (see App. B).
For the LCD display the temperature range is -4 °F to +185 °F (-20 °C to +85 °C).
See temperature diagrams on page A-6.
-40 °F to + 176 °F ( -40 °C to +80 °C).
Standard: -40 °F to +302 °F ( -40 °C to +150 °C).
HTHP: -76 °F to +752 °F ( -60 °C to +400 °C).
HP: -76 °F to +392 °F ( -60 °C to +200 °C).
See temperature and pressure diagrams on page A-4.
(4)
Standard
: Full vacuum to 580 psig ( -1 to 40 Bar).
HTHP: Full vacuum to 5000 psig (-1 to 345 Bar).
HP: Full vacuum to 5000 psig (-1 to 345 Bar).
See temperature and pressure diagrams on page A-4.
0 - 100 % relative humidity
NEMA 4X, IP 66.
FCC part 15 (1998) subpart B and R&TTE (EU directive 97/23/EC). Considered to be
an unintentional radiator under the Part 15 rules.
Yes.
IEC 721-3-4 Class 4M4.
Emission and Immunity: meets EN 61326-1 (1997) and amendment A1, class A
equipment intended for use in industrial locations if installed in metallic vessels or
still-pipes.
When rigid/flexible single and twin lead probes are installed in non-metallic or open
vessels, influence of strong electromagnetic fields might affect measurements.
Meets EN 61000-4-4 Severity Level 4 and EN 61000-4-5 Severity Level 4.
Complies with 97/23/EC article 3.3.
Compliance.
Compliance.
Reference Manual
00809-0100-4811, Rev CA
February 2006
(1)
and O-ring materials (model code 1)
(1)
and O-ring materials (model code 2)

Advertisement

Table of Contents
loading