Installation; Preparation; Marking The Installation Holes - HP D7171A - NetServer - LPr Installation Manual

Compaq 4000/7000 racks installation guide
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

3 Installation

This section contains detailed instructions for installing an HP NetServer
NetServer LH 3r, LH 4r, LH 3000r, or LH 6000r in the model 4000/7000 series of
Compaq rack enclosures.

Preparation

Before beginning the installation of the NetServer into the rack, you must prepare
the rack and the NetServer.
Determine the location at which the NetServer is to be installed in the rack
enclosure. Mark the bottom and top of this location on the rack columns.
The HP NetServer measures 8 EIA units tall.

Marking the Installation Holes

Mark two holes on each of the four columns to use for the bar nuts and screws that
hold the slides to the columns.
When marking the holes, mark the outer surface of the column see Figure 3-1; on
the front columns, this is the column surface facing forward; on the rear columns,
this is the surface facing rearward. Use tape or a marker pen to mark the
appropriate holes on each column.
To mark the slide mounting holes refer to Figure 3-1:
1. Count up from the top of the unit below, marking the 20th and 22nd holes.
2. Repeat for all four columns.
NOTE
Do not place nuts or screws in the holes at this time, only mark
them.
7