Configuring a Serial-Connected Master: Other IA Protocol

Configuring a Serial-Connected Master: Other IA Protocol

When to Use

Procedure

66
Use this procedure when the device connected to the serial port is a
master that is using a "non-supported" serial-port protocol, that is, the serial
port protocol is not Modbus ASCII, Modbus RTU, DF1 Half-Duplex, DF1
Full-Duplex, FINS, Hostlink, CompoWay/F, or a protocol that meets the
definition of a "user-defined" protocol.
1. Access the web interface by entering the device server IP address in a
browser's URL window.
2. Log in to the device server as root. The default password is dbps.
3. From the main menu, choose Configure > Port.
4. From the Port configuration page, set the Device type to Modem In,
adjust other serial port communication parameters as required by the
connected master, then choose Submit.
The Terminal type field does not matter.
5. If you want to configure the port to launch an automatic connection to
the slave, click Advanced.
6. Choose Enable Autoconnect.
7. Specify the IP address of the slave.
8. Specify a TCP port to use for this connection. If this is a connection to
another device server, use 2101 as the TCP port number.
9. If you want the autoconnection to launch immediately, choose Force
DCD.
10. Choose Binary Mode.
11. If you want to enable UDP sockets (instead of TCP sockets), choose
UDP Serial, use the online help for information on completing
configuration task.
12. When you complete configuration, click Submit.
Chapter 4 Configuring Industrial Automation (IA)