Configure Digi RPM Settings
90
6. Optionally, set thresholds and alarms for the Digi RPM and click Apply.
Digi RPM can be configured to generate an audible alarm and an
SNMP trap when either of the following types of thresholds are reached
on the unit:
Current Alarms (amps): The current alarm threshold monitors the
electric current on the Digi RPM. You can set up to four thresholds,
depending on the number of current sensors on the Digi RPM.
When the sensor's specified amperage level is reached, the Digi
RPM will emit an audible alarm. Current alarm thresholds are
configurable in the range of 0.1 to 99.9 Amps.
To generate current alarm threshold SNMP traps, you must also go
to the System > SNMP configuration page and select Generate
Power Unit Current Threshold Traps option, and specify a
destination IP address for the SNMP trap.
Temperature (°C): This alarm threshold monitors the temperature
on the Digi RPM. You can set up to four thresholds, depending on
the number of temperature sensors on the Digi RPM. When the
sensor's specified temperature is exceeded, the Digi RPM will emit
an audible alarm.
Temperature alarm thresholds are configurable in the range of 0.1 to
99.9 °C
To generate temperature threshold traps, you must also go to the
System > SNMP configuration page, select Generate Power Unit
Temperature Threshold Traps option, and specify a destination IP
address for the SNMP trap.
Chapter 9 Digi Remote Power Manager (Digi RPM)