ACT ACTPRO 4000 Operating And Installation Instructions page 52

Access control system
Hide thumbs Also See for ACTPRO 4000:
Table of Contents

Advertisement

Alarm Panel
Note:
0V line of ACT Controller
Disarmed
system is connected to
the 0V of the alarm
panel.
0V
N/O
Input
COMM
Connect AUX Relay output from controller to
arm input on panel. The AUX relay can be set to
pulse of toggle. Toggle by programming the AUX
Relay time to zero.
NOTE: If multiple doors are required to lock when the
alarm is armed, then it is required that each door
monitor the alarm status. If the Alarm is not being
monitored then only the door that is wired to control
the alarm panel will lock.
Alarm Panel Wiring Diagram
PUSH
BUTTON
DOOR
CONTACT
INPUT
0V
OP2
OP3
STEPS TO PROGRAM THE ACT Controller FOR ARM/DISARM
1.
Complete the wiring in the diagram above for the door that the system will be Arm/Disarmed from.
2.
Enter the installer Menu and select the Door Settings submenu. Then select the Door number
of the reader that User will arm and disarm from.
Optional signal from the
3.
In the Alarm section of Door Settings set the "ARM Intruder" option to Yes.
alarm panel to indicate armed
or disarmed status. If 0V is
4.
If the Alarm Panel provides a signal to indicated the arm/disarm status then
connected to AUX Input,
in the Operation section of the Door settings set the "Monitor Arming" Option to Yes
the panel is armed.
If the alarm panel does not provide a status signal then ensure the "Monitor Arming"
option is set to No.
5.
Exit the installer menu and enter the Operator menu and select "User Settings" chose the
"Assign Options" submenu. Select the User that will be allowed to arm and disarm the panel and
set the option "AUX ARM/DISARM" option bit. Make sure the user is enabled.
6.
The configuration is complete. The User can arm the system at the reader by first pressing the "tick" key
followed by presentation of a card. Once the Alarm is armed (as monitored by the AUX IP) the Door will lock.
7.
Disarming is achieved by again pressing the "tick" key and presenting the Card.
Common the 0V line of
each Controller
AUX
5A 250VAC
5A 30VDC
N/C
C
N/O
N/C
C
N/O
AUX RLY 1
RELAY 1
ACT Controller
While the AUX input is active (connected to 0V), the door is locked.
DOOR I/O
5A 250VAC
5A 30VDC
TAMPER
MAINS
+12V
1 2 3 4 5 6 7 8
0V
On
W P 2
Address
Door 3