ACTpro 4000 Operating Instructions
__________________________________________________________________________
PIN Required
For the duration of the assigned time zone, a valid PIN code must be
entered after any card is presented. This overrides any PIN required
option that may be set for any group or user.
Any Card
For the duration of the assigned time zone, any card presented will be
granted access as long as it contains Track 2 data, even if it would
not normally be granted access.
For the duration of the programmed time zone, the user
Activate OP2
programmable output OP2 is active.
Activate OP3
For the duration of the programmed time zone, the user
programmable output OP3 is active.
For the duration of the programmed time zone, the 1A auxiliary relay
Activate AUX
output AUX is active.
PIN Only
For the duration of the programmed time zone, the reader is disabled,
and access is granted only by entering a valid PIN.
For the duration of the programmed time zone, either a valid PIN or a
PIN or Card
valid Card will allow access.
While this time zone is active, two valid cards must be presented to
Twin Users
gain access. Used in high security applications where two people
must be in the room at the same time.
During this time zone a door will revert to normal state, i.e. requires
Normalise Doors
valid card to gain access. Use this to ensure door is closed at certain
times in case it is left toggled open.
This menu allows the installer to configure how the controller communicates with externally
connected devices or over a network. It is used primarily to configure the address of the
ACTpro 4000. It is also used to enable remote doors.
Set Address
This option allows the address of the controller to be set when it is operating in a networked
system or when directly connected to a PC. The valid address may be from 1 to 255 and
corresponds to the number of the controller as configured in ACTWin pro.
Comms Speed
Communications on the controller defaults to 9600 baud. However speeds of 19200 and
57600 baud can be selected from this menu. All speeds are permitted for direct connect to a
PC. 9600 and 19200 baud are permitted on the single-line RS485 networked interface. 9600
baud only is permitted on the ACT 4-Line RS485 interface.
__________________________________________________________________________________
Communications
25
1.00