17.1 Introduction

The PC4020CF is a UL/ULC Listed panel for [1] Central
and Remote Station Fire Monitoring [2] Local and Central
Station Burglary Alarm Monitoring and [3] Access Control
(in conjunction with PC4820). When used as a fire panel, all
fire functions must be configured to take priority over Bur-
glary, Access Control and other auxiliary functions.
The PC4020CF has a number of system functions estab-
lished as default values. These functions must be main-
tained to ensure the Life-Safety integrity of the installation
meets all applicable codes and standards.
To ensure an appropriate installation, all applicable NFPA,
UL and local codes and standards should be reviewed.
Local AHJ (Authority Having Jurisdiction) should also be
consulted prior to installation to determine specific local
requirements for a fire alarm installation.
Information in this manual is intended to describe the fire
functionality of the equipment. Further information on the
overall system is contained in the companion manuals for
this product and must be consulted for a full understanding
of operation, installation and programming.
This manual lists a number of alarm initiating and alarm
notification devices for use with this equipment. Use of
devices other than those listed herein must be carefully
evaluated for compatibility. 2-wire smoke detectors other
than those listed in this manual cannot be used without
voiding the listing status of the equipment.
Remote downloading of a fire panel, once it has been put
into operation and is protecting a premises, is severely lim-
ited. See the Upload/Download section of this manual for
information on this topic.

17.2 Hardware Description and Specifications

PC4020CF - Main Panel
• One - PC4050CR – red cabinet 14.8" x 12.0" x 4.9" with
space for two 12V, 7Ah sealed lead-acid rechargeable
battery
• One - PC4020 Main Control Module which includes:
• 16 zones programmable for Fire or Burglary
• Two Programmable Outputs (each programmable as
an addressable device loop):
• 12 V
, 50 mA max. each (standard output) or
DC
• 12 V
, 170 mA max. each (addressable loops)
DC
• One switched AUX Power Supply – 12 V
max.
• One unswitched AUX Power Supply – 12 V
mA max.
NOTE: Refer to the PC4020 Installation Manual for compat-
ible devices.
• One Supervised Bell circuit – 12 V
• Supervised Battery Charger – 12 V
ing current (continuous); 400mA max.
• Supervised Telephone Communicator (connects to
PC4701 module)
• One - Power Transformer – 16.5 V
• One - Hardware package which includes:
• 16 EOL resistors (5,600Ω)
, 120 mA
DC
, 120
DC
, 700 mA max.
DC
, 350 mA charg-
DC
, 40 VA
AC
• One Black cabinet plug
• One green grounding strap
• Mounting hardware for the PC4020A PCB
NOTE: The ESCORT4580 cannot be used with PC4020CF
panels.
PC4701 - Fire Module
• One – Two-Wire Smoke detection zone
• Class 'B'/Style 'B'
• Accommodates up to 30 – 12 V
tors.
• One – Waterflow zone – Class 'B'/Style 'B'
• Two – Supervised Communicator outputs
• One – Fire Alarm actuated relay:
Form 'C', rated 2A, 30 V
DC
• One – Fire Trouble actuated relay:
Form 'C', rated 2A, 30 V
DC
• Terminal connections for house telephone
• Hardware to mount the module to the sidewall of the
PC4050CR enclosure
T-Link Local Area Network Communicator
The T-Link Local Area Network Communicator provides an
efficient method of communicating via a Local Area Net-
work (LAN). See the T-Link Installation Manual (part no.
29001007) for more details.
PC4702BP - Bell Panel
• One - PC4052CR Red cabinet – 12" x 12" x 5" with space
for two 12 V
, 4.0Ah sealed lead-acid rechargeable bat-
DC
teries
• One PC4702 Dual Bell Zone module which includes:
• Two supervised Class 'B'/Style 'Y' Bell outputs – 24
V
FWR, 1.8A each. Outputs supervised for opens,
DC
shorts and ground with self-restoring short protection
• Supervised battery charger, 24 V
current for sealed lead-acid rechargeable batteries
• Power transformer – 28 V
inet)
• Combus connection terminals
• Hardware for mounting PC4702 module.
LCD4520 - Fire Keypad
Standard LCD keypad with red bezel for use with the
PC4020CF
LCD4521 - Fire Keypad with Function Keys
LCD keypad with red lens and five function keys:
• Silence Trouble
• Silence Bells
• Fire Reset
• Fire Drill
• Lamp Test
NOTE: At least one LCD4520 or LCD4521 keypad must be
used with the PC4020CF.
NOTE: Maximum keypad current draw 55mA
2-wire smoke detec-
DC
, 350 mA charging
DC
, 175 VA (mounted in cab-
AC
49