HINT: If you program more than one PGM for the same
HINT
HINT
HINT
command output (eg. command output 1), make sure that
either:
a) the PGMs are enabled for all the same partitions
OR
OR
OR
OR
b) the partitions the PGMs are enabled for do not overlap.
If the 'Inv Cmd Out #X'
'Inv Cmd Out #X' system toggle option is enabled, the
'Inv Cmd Out #X'
'Inv Cmd Out #X'
output will be inverted (i.e. the output will normally be
energized, and will de-energize when activated). (Ref #
[000200]) By default, this option is only enabled for Com-
mand Output #2.
If the 'Sen Rst Cmd#2'
'Sen Rst Cmd#2' partition toggle option is enabled,
'Sen Rst Cmd#2'
'Sen Rst Cmd#2'
the output programmed as Command Output 2 will reset
all smoke detectors connected to it when activated (Ref #
[0100XX01]). The keypad will display the Command Out-
put #2 label while the smoke detectors are resetting. If there
is no fire condition present, the smoke detectors will return
to normal operation after being reset.
NOTE: If you have programmed fire zones on a partition,
you should also enable the 'Sen Rst Cmd#2' partition toggle
option.
Command Output Labels
Ref #: [0100XX06YY] where XX = partition number (01-08),
YY = command output number (01-08)
Program command output labels in this section. All system
display labels are programmed in a similar fashion. For
instructions on programming labels, see 5.4 'Zone Program-
ming'.
Police Output (46)
The output will activate when a Cross Zone/Police Code
Alarm reporting code is transmitted for any of the selected
partitions. It will remain active until a valid access code is
entered on any of the selected partition keypads.
Holdup (47)
The output will activate when a holdup zone on any of the
selected partitions is in alarm. It will remain active until a
valid access code is entered on any of the selected partition
keypads. A tamper or fault on a holdup zone will not acti-
vate the output.
Fire Zone Tbl. (48)
The output will activate when a fire zone is bypassed, or
when a fire zone trouble or fault condition is detected. The
output will deactivate when the zone is unbypassed or the
trouble/fault is restored.
Steady Fire (49)
The output will turn on steady upon any alarm from a Fire
type zone with the Audible zone attribute enabled.
Temporal Pattern Fire (50)
The output will follow the standard temporal pattern upon
any alarm from a Fire type zone with the Audible zone
attribute enabled. The temporal pattern is 0.5s ON, 0.5s
OFF two times and then 0.5s ON and 1.5s OFF. This pattern
is repeated until the signals are silenced.
NOTE: PC4204/PC4204CX/4216 v2.1 or higher is required for
this option.
CSFM Fire (51)
The output will follow the California State Fire Marshal
pattern upon an alarm from a Fire type zone with the Audi-
ble zone attribute enabled. The CSFM pattern is 10s ON
and 5s OFF. This pattern is repeated until the signals are
silenced
Pulsed Fire (52)
The output will activate upon an alarm from a Fire type
zone with the Audible zone attribute enabled. The output
will pulse ON for 0.5s and OFF for 0.5s. The pulsing will
continue until the signals are silenced.
36
Fire Strobe (53)
The output will turn on steadily upon an alarm from a Fire
type zone with the Audible zone attribute enabled. The out-
put will not turn OFF upon signal silence but only on a suc-
cessful Fire Reset.
Ground Fault (54)
The output will activate when the PC4020 detects a Ground
Fault trouble. The output will deactivate when the trouble
is cleared.
Common Fire Tbl. (55)
The output activates when any of the following troubles is
detected by the panel. The output deactivates when the
trouble is cleared:
• Any system AC or battery trouble (PC4020, PC4820,
PC4204/PC4204CX, PC4702, PC4850*, Alternate Commu-
nicator*)
• Any system communicator trouble (TLM1, TLM2, FTC,
LINKS, Alternate Communicator*)
• Ground Fault trouble
Bell Trouble (56)
The output will activate for a trouble (open or short) on any
supervised system bell output (PC4020 or PC4702). The
output will deactivate when the trouble is cleared.
AC Status (57)
The output will be active when AC is present on the PC4020
as well as all enrolled modules (PC4204/PC4204CX,
PC4820, PC4702, PC4850*, Alternate Communicator*). The
output will deactivate when an AC Fail trouble condition is
generated. This output will follow the 'AC Fail Delay,' if pro-
grammed (see 10.9 'Transmission Delay').
Partition Status Alarm Memory (58)
The output will activate when any of the selected partitions
are armed. It will deactivate when all selected partitions are
disarmed. If an alarm, tamper or fault occurs on any of the
assigned partitions, the output will flash for the remainder
of the armed period. If the partition is disarmed, the output
will flash until the alarm is acknowledged, or the bell time-
out period expires.
Card Used PGM Type (59)
When this output type is programmed, the panel will
prompt the installer to enter the user number that this out-
put will activate for. The output will be active for the
amount of time programmed in the Pulse Timer whenever
an Access Granted event is sent for that user. If pro-
grammed for 000 the output will toggle On/Off depending
on its initial state.
Battery Test Output (60)
Whenever partition one is disarmed the panel will perform
a 30-second battery test. During this battery test any PGM
output programmed as Battery Test will activate for the
duration of the battery test. The output is intended to be
used to switch a load onto the battery circuit.
Seismic Test (61)
This output type will activate for 15 seconds upon disarm-
ing or when a seismic schedule becomes active. The seis-
mic test will be active for forty seconds. The zones defined
as seismic zones will be tested for an 'open condition' dur-
ing the first twenty seconds and tested for a 'restore' during
the last twenty seconds. This output can be used on a sys-
tem that has Seismic Zone types defined. This is only a test-
ing output that will trigger the zone into alarm.
• The panel will ensure that all zones that are pro-
grammed as a Seismic Sensor have gone into alarm.
• The Seismic Sensor Output will then be deactivated and
the panel will wait 10 seconds allowing the Seismic Sen-
sors to restore.
• The panel will then ensure that all zones that are pro-
grammed as a Seismic Sensor have restored.