Installation Manual

PC1555 CP-01
PC1555 CP-01 Version 3.2
DLS2002 and higher

Advertisement

Table of Contents
loading

Summary of Contents for DSC PC1555 CP-01

  • Page 1: Installation Manual

    This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read. Now classified in accordance with ANSI/SIA CP-01-2000 (SIA-FAR) Installation Manual PC1555 CP-01 PC1555 CP-01 Version 3.2 DLS2002 and higher...
  • Page 2 NOTES...
  • Page 3 ESCORT5580 v3.0, and the PC5936 v1.0. Refer to the Escort5580 v3.0 and PC5936 v1.0 Installation Manuals for further information. Loop Response The PC1555 CP-01 v3.2 and higher can configure any or all onboard zones for 36 ms Loop Response (see Section [030] - Fast Loop Response, Pg 29). T-Link...
  • Page 4 PC1555 CP-01 Installer Programming Quick Reference Chart SIA False Alarm Reduction Minimum requirement system for SIA-FAR Installations : PC5208 Low Current PGM Output Module The following optional accessory modules also bear the SIA FAR classification and • 1 PC1555 CP-01 Control Panel may be used if desired.
  • Page 5: Table Of Contents

    Section 1: Introduction Viewing Programming ..........10 About the PC1555 CP-01 System ......... 1 Section 4: Keypad Commands About the PC1555 CP-01 Manual Set ......1 Arming and Disarming ..........11 Main Panel Specifications ..........1 [*] Commands ............12 Additional Devices ............
  • Page 6 PC1555 CP-01 Wiring Diagram NOTE: Remove CON1 when using PGM2 for 2-wire smoke...
  • Page 7: Section 1: Introduction

    Section 1: Introduction 1.1 About the PC1555 CP-01 System Audible Alarm Output: The PC1555 CP-01 is a high end security system. It sup- • 700mA supervised bell output (current limit 3 Amps), ports up to 32 zones, and 32 users.
  • Page 8: Additional Devices

    PC5200 Power Supply Output Module System Supervision Features The PC5200 can provide up to 1 Amp of additional power The PC1555 CP-01 continuously monitors a number of for modules or devices connected to the control panel. Up possible Trouble conditions including: to 4 modules can be connected to the system.
  • Page 9 PC4050C - alternate main control cabinet (Household PC4050C - PC4050C - keypad. Dimensions 208mm x Fire & Burglary) for the PC1555 CP-01 main panel. 115mm x 18mm / 8.2” x 4.5” x Dimensions 305mm x 376mm x 125mm / 12.0” x 14.8” 0.25” approximately.
  • Page 10: Section 2: Installation And Wiring

    Section 2: Installation and Wiring The following sections provide a complete description of how to wire and configure devices and zones. 2.1 Installation Steps Step 10 Testing the System The following steps are provided to assist with the instal- Test the panel completely to ensure that all features and lation of the panel.
  • Page 11: Wire Routing For Power & Non-Power Limited

    • shielded wire is not necessary unless wires are run in an area that may present excessive RF noise or interference Example of Keybus Wiring For example, if you are installing a PC1555 CP-01 with a Module (A) is wired cor- LINKS1000/GSM1000 and a PC5936 intercom module,...
  • Page 12: Keypad Assignment

    Refer to the following chart: PC5208 VAUX: 250 mA. Subtract for each device connected. Subtract the Keypad Light Module/Device Present total load on this terminal from the PC1555 CP-01 Keypad 1 VAUX/Keybus output. Keypad 2 Keypad 3 Other Devices Keypad 4 Read the manufacturer’s literature carefully to determine...
  • Page 13: Removing Modules

    If a module is connected but does not show as being present, it may be due to any of the following reasons: • it is not connected to the Keybus • there is a Keybus wiring problem • the module is more than 1,000'/305m from the panel •...
  • Page 14: Keypad Zones

    For a complete description of how fire zones operate, see NOTE: Keypad zones cannot be used for 24-hr Supervisory section ’Basic Programming PWS Sect 3’ . or LINKS1000 Answer. LINKS 2X50/LINKS 3000/Skyroute™ Fire Zone Wiring - 2-wire Smoke Detectors Refer to the LINKSX50, LINKS3000 and Skyroute™ If PGM2 has been programmed for 2-wire smoke detector connection ( see section ’Basic Programming PWS Sect 3’...
  • Page 15: Section 3: How To Program

    Section 3: How to Program The following section of the manual describes how to 1 = A 2 = B 3 = C 4 = D 5 = E 6 = F enter Installer Programming and how to program the var- After the correct Hex digit is entered the Ready light will ious sections.
  • Page 16: Viewing Programming

    3.5 Viewing Programming LED and LCD5501Z Keypads Any programming section can be viewed from an LED or LCD5501Z keypad. When a programming section is entered, the keypad will immediately display the first digit of information programmed in that section. The keypad displays the information using a binary for- mat, according to the following chart: See Hex data entry instructions...
  • Page 17: Section 4: Keypad Commands

    Section 4: Keypad Commands Use any system keypad to enter commands, or to program the PC1555 CP-01 security system. The LED keypad uses function and zone indicator lights to represent alarm functions and status. The LCD keypad provides a written description on the liquid crystal display and uses function indicator lights to communicate alarm status to the user.
  • Page 18: Commands

    between this information and the event itself. Use the Master code or Supervisor codes must be used to arrow keys (<>) to scroll through the events in the buffer. access this feature. When you have finished viewing the event buffer press NOTE: If a 24-hr zone is bypassed, ensure that the zone is the [#] key to exit.
  • Page 19 3. Enter the attribute number to toggle it on or off. panel was disarmed (24-hr zones). Instructions on view- The programmable attributes are as follows: ing alarms in memory are located in the PC1555 CP-01 • Attributes 1-2 Attributes 1-2 Attributes 1-2 Attributes 1-2: For Future Use.
  • Page 20: Function Keys

    4.3 Function Keys LCD Keypad User Functions There are five function keys on the PC1555 CP-01 key- Additional features are available using on the LCD key- pads labelled Stay, Away, Chime, Reset and Exit. The pad. These features do not have numbers assigned. Use operation of these keys is described below.
  • Page 21 ’Chime’ - Door Chime On/Off be entered before the panel will allow User Functions to be performed (section 4.2 ‘[*] Commands‘) . Pressing the key will toggle the Door Chime feature ON or OFF. One solid beep means the feature has been dis- [13] - [*]+[7]+[1] Command Output Option 1 abled, three short beeps means it has been enabled.
  • Page 22: Features Available For The Lcd5500Z/Lcd5520Z

    [24] - Recall Bypass Group This function key will recall zones in the Bypass Group . This group is programmed by the user in the [*][1] Bypass menu. The function key will follow the Code Required for Code Required for Code Required for Code Required for Bypass...
  • Page 23: Section 5: Programming Sections

    Opening/Closing Communicator Call Directions Restore PC5132 to Factory Default Programming System Maintenance Communicator Call Directions Restore PC5400 to Factory Default Programming System Test Transmissions Communicator Call Directions Restore PC5936 to Factory Default Programming Communication Variables Restore PC1555 CP-01 to Factory Default Programming...
  • Page 24: For The Record Pws Sect 1

    5.1 For the Record PWS Sect 1 This Section identifies the client, installation date, Installer Code, hardware configuration and programming summary for each zone. Remove these pages and retain for reference. 5.2 Keypad Programming PWS Sect 2 Refer to Section 2.6 ‘Keypad Assignment’ 5.3 Basic Programming PWS Sect 3 [001]-[002] - Zone Definitions These sections require 16 2-digit entries.
  • Page 25 [001]-[002] ZONE DEFINITIONS Option Zone Type Description LINKS Answer Provides the LINKS1000 with a forced answer for downloading. The Restored state of this zone type is 5.6KΩ, and the open state causes the panel to answer. See the LINKS1000 Installation Manual for wiring instructions. When the zone is violated, the panel will seize the telephone line.
  • Page 26 PGM Attribute Programming ....Section [501]-[564] code indicated in the table below. Programmable outputs are available on the following devices: • PGM 1, PGM 2 on the PC1555 CP-01 main board [009] - [011] PROGRAMMABLE OUTPUT OPTIONS Option...
  • Page 27 [009] - [011] PROGRAMMABLE OUTPUT OPTIONS Option Output Description Latched System Event This output will activate when any of the selected system events (alarms) occur on the system. In the armed state, (Strobe) the output will deactivate only once the system is disarmed. This output will activate when the programmed events occur on the system.
  • Page 28 [012] - Keypad Lockout Options the programmed duration. When any keys are pressed, an error tone will sound. The panel can be programmed to ‘lockout’ keypads if a series of incorrect access code entries is made. After the To program ‘Lockout Duration’, enter a time from 000 to Number of Invalid Codes Before Lockout Number of Invalid Codes Before Lockout has been Number of Invalid Codes Before Lockout...
  • Page 29 Option Definition On/Off Description Bell During Auto- Bell Squawk During Auto-arm Enabled. The bell output will sound a single squawk every 10 sec- onds during the Auto-arm Pre-alert time. This will inform anyone on the premises that the system is being armed.
  • Page 30 Option Definition On/Off Description Telephone Line Telephone Line Monitor enabled. The TLM function will be active and the system will indicate a Monitor Trouble #3 condition when using the [*][2] View Trouble Conditions command. Telephone Line Monitor disabled. The TLM function will be shut off and telephone line troubles will not be indicated by the system.
  • Page 31 Option Definition On/Off Description Double Hit Double Hit Enabled. Two alarms from the same zone within the Cross Zone Timer Duration will cause the Police Code or Cross Zone to be logged and transmitted. Double Hit Disabled. Two alarms from the same zone will not cause the Police Code or Cross Zone to be logged and transmitted.
  • Page 32: Advanced Programming Pws Sect 4

    When an audible non-fire zone goes into alarm with this feature enabled, the PC1555 CP-01 will sound the alarm condition via the bell outputs, but every 15 seconds (as programmed in the Alarm Tone Period – Section [178]) it will silence the bell outputs and the PC5936 speakers will verbally annunciate the alarm condition ’Alarm Zone 4’...
  • Page 33 The default value is 007 attempts. Valid entries are 001-015. the arming. When the postpone time expires, the panel NOTE: The PC1555 CP-01 will not allow more than 15 dial- Auto-arm Pre-alert will be re-initiated. The Auto-arm can ing attempts to a single phone number. If a value higher be postponed multiple times.
  • Page 34: Partition & Zone Programming

    NOTE: Option[9], Section [101]-[132] must be enabled for [199] - Auto-arming Pre-Alert Time the Cross Zoning feature to function. Each zone has the abil- This section allows programming of the standard Auto- ity to individually protect the intended area. Cross Zoning is arm Pre-alert duration.
  • Page 35 [301] - First Telephone Number Reporting codes are two digits and can use hexadecimal digits A through F. To disable a reporting code, program it [302] - Second Telephone Number as FF (default setting) or 00. For a complete description of [303] - Third Telephone Number reporting codes which can be programmed and lists of Automatic Contact ID and SIA format codes, see section...
  • Page 36 Alarm Cancelled: this reporting code will be sent if a valid Arming via Keyswitch access code is entered during the Alarm Cancel window. Away Function Key Arming If a valid access code is entered during this window, then Arming with the Maintenance Code. the Alarm Cancelled event is logged and sent.
  • Page 37 • Fire Zone Trouble (Zones 1-32) AC Power Failure Low Battery • Battery Trouble (PC1555 CP-01, PC520X) AUX Output Trouble Output #1 on the PC5200 / • Fire Zone Alarm (Zones 1-32, Two-Wire Smoke PC5204 power Supply/Output Module after a Trouble •...
  • Page 38 SIA (Level 2) direct the call to a telephone number with the Pager for- mat selected the panel will attempt to page. SIA is a specialized format that will communicate infor- mation quickly using frequency shift keying (FSK) rather When calling a pager extra digits will be required to make than pulses.
  • Page 39 If Contact ID Sends Automatic Reporting Codes Contact ID Sends Automatic Reporting Codes Contact ID Sends Automatic Reporting Codes is Contact ID Sends Automatic Reporting Codes digit reporting code. The 2-digit identifier is pre-pro- selected, the panel will automatically generate a reporting grammed by the panel.
  • Page 40 [377] - COMMUNICATION VARIABLES Swinger Shutdown (Alarms & Restores) This value defines the number of attempts (alarm and restoral pairs) per zone that the communicator will make before it shuts down for that zone (’swinger shutdown’). Program 001 or 002 in this entry. When programmed as 000, the communicator will shut down after 2 Alarm/Restoral pairs. Different limits can be programmed for Zone Alarms, Zone Tampers and Maintenance signals.
  • Page 41 [380] - FIRST COMMUNICATOR OPTION CODES Option Communicator Code On/Off Description Communications Communicator Enabled. The system’s communicator will be enabled and all events with reporting codes will be reported to the monitoring station. Refer to the Telephone Number, reporting code and Call Direction Programming Sections. Communicator Disabled.
  • Page 42 [381] - SECOND COMMUNICATOR OPTION CODES Option Communicator Code On/Off Description SIA Reporting Codes SIA Sends Programmed Reporting Codes. This option is for use with the SIA communication format.). If 00 is programmed in the reporting code section, the event will not be communi- cated.
  • Page 43: Downloading Options Pws Sect 7

    [390]-[393] LINKS Preambles NOTE: If this Special Preamble is programmed, it will be inserted before the Regular Preamble of ALL telephone num- Downloading can be performed through the LINKS1000 bers. Hex digits D and E are not supported for Preamble pro- cellular communicator if the telephone line is discon- gramming.
  • Page 44 The Download Access Code Download Access Code Download Access Code and Panel Identifier Code Download Access Code Panel Identifier Code Panel Identifier Code Panel Identifier Code need to program the LINKS1000 Preamble LINKS1000 Preamble LINKS1000 Preamble with the LINKS1000 Preamble are for security and proper identification.
  • Page 45: Programmable Output Programming Pws Sect 8

    To determine the value to be programmed in this section perform the following: The PC1555 CP-01 has an 8-bit toggle field per output. The status of the first bit of the 8-bit toggle field deter- • Monitor the time lost by the panel over a period of time.
  • Page 46 [701] FIRST INTERNATIONAL OPTION CODES Option International Code On/Off Description 50 Hz AC. - The incoming AC power cycles at 50 Hz. 60 Hz AC. - The incoming AC power cycles at 60 Hz. Time Base The timebase is the internal crystal oscillator. In cases of unstable AC power input, the internal crystal can be used to keep the most accurate timebase.
  • Page 47: Module Programming Pws Sect 10

    [703] - Delay Between Dialing Attempts NOTE: If there is no zone activity on the system for 15 min- utes, the system will end the Walk Test and return to the For standard (force) dialing, the panel will go off-hook, normal state.
  • Page 48 2. To disable Installer Lockout, enter section [991]. When this section is successfully entered, all program- 3. Enter the Installer Code. ming for the PC1555 CP-01 will be returned to the factory 4. Enter section [991] again. defaults. The programming for the Escort5580(TC),...
  • Page 49: Section 6: Listing Requirements

    The control panel must be in the attack-resistant enclosure The alarm sounding device (bell) must be located where it can be heard by (DSC Model CMC-1 or PC4050CAR). the person or persons responsible for maintaining the security system dur- ing the daily arming cycle.
  • Page 50: Appendix A: Reporting Codes

    Appendix A: Reporting Codes The following tables contain Contact ID and Automatic SIA Format - Level 2 (Hardcoded) SIA format reporting codes. For more information on The SIA communication format used in this product fol- reporting code formats and notes about individual lows the level 2 specifications of the SIA Digital Commu- reporting codes, (see section 5.6 ‘Communicator Pro- nication Standard - October 1997.
  • Page 51 Opening (disarming) using one of the following methods: key- (4) AA OP-00 switch, maintenance code, DLS software, wireless key [345]-[346] Battery Trouble/Restoral PC1555 CP-01 battery is low/battery restored MA/R (3) A2 YT-00/YR-00 [345]-[346] AC Line Trouble/Restoral AC power to control panel is disconnected or interrupted/AC...
  • Page 52 Table2: Contact ID Zone Alarm/Restoral Event Table 3: SIA Format Automatic Zone Alarm/Restoral Codes (as per ADEMCO): Codes Program any of these codes for zone alarms/restorals when using Contact ID the standard (non-automatic) Contact ID reporting format. SIA Auto Rep Auto Rep Codes* Medical Alarms...
  • Page 53: Fcc Compliance Statement

    Equipment Maintenance Facility • Increase the separation between the equipment and receiver. If trouble is experienced with this equipment PC1555 CP-01, for repair or warranty infor- • Connect the equipment into an outlet on a circuit different from that to which the mation, please contact the facility indicated below.
  • Page 54: Limited Warranty

    It is freight cost to the repair centre; (ii) products which are not identified with DSC's product label and lot num- important that all system users be trained in the correct operation of the alarm system and that they know ber or serial number;...
  • Page 55 NOTES...
  • Page 56 PC1555 CP-01 Module Compatibility Module Compatible? Comments Classic Escort (VPM-1) DLM-1 DLM-4 v1.x DLM-4 v1.0L DLM-7 Escort5580 v3.0 LCD5500 v1.X No Keypad zone support. Some display messages not supported. Can only be used on Partition 1 and Partition 2, and the first 32 zones.